Commissioning
Gammapilot M FMG60 FOUNDATION Fieldbus
60
Hauser
7.3
Basic setup
7.3.1
"Present date" (*01)
Local display
Present date *01
17.11.04 _____10:30
DD.MM.YY ____ HH:MM
This function is used to enter the date and time of the basic setup. Each of these values
must be confirmed by pressing after entering the value.
7.3.2
"Beam type" (*02)
Local display
Beam type *02
✓
Standard/cont.
Modulated
This function is used to specify whether the radiation source used emits radiation
continuously or whether it is modulated (for gamma radiography suppression).
• Standard/continuous (permanent, continuous radiation)
• Modulated (modulated radiation source)
7.3.3
"Isotope" (*03)
Local display
Isotope *03
✓
137 Cs
60 Co
No compens.
This function is used to specify which isotope is used for the measurement. The
Gammapilot M needs this information for decay compensation.
7.3.4
"Operating mode" (*04)
Local display
Operating mode *04
✓
Stand alone
Master
Slave
This function is used to specify in which operating mode the Gammapilot M will be used.
The operating mode can only be selected once. After this, the function is
automatically locked and can only be unlocked by resetting the Gammapilot M ("Reset"
(*A3) function).