• "Level" operating mode, "Level Easy Pressure" level selection: The PRESSURE EMPTY and PRESSURE FULL
parameters are only displayed for the "Dry" CALIBRATION MODE. If you have performed a wet calibration,
you subsequently have to select the "Dry" option by means of the CALIBRATION MODE parameter. You
can read out the corresponding values for the PRESSURE EMPTY and PRESSURE FULL parameters here.
• The sensor can only be recalibrated by Hauser Service.
As the parameters for a sensor recalibration are not reset with the "7864" reset code, the parameters have to
be checked prior to locking via the SAFETY LOCK menu.
Checks
After entering all the parameters, check the safety function prior to the locking sequence by means of the
SIMULATION MODE parameter or by approaching the limit pressure, for example. (
→
Operating Instructions
BA274P SIMULATION MODE parameter description.)
The entire safety function should be checked after each change to the Deltapilot S as part of a safety function,
e.g. a change to the orientation of the device or the configuration.
Locking/Unlocking
#
Warning!
After entering all the parameters and checking the safety function, the operation of the device must be locked
since changes to the measuring system or parameters can affect the safety function.
Increased security during parameter entry
Locking
With the "Increased security during parameter entry" method, the device is locked by a password at the end of
the locking sequence.
16 ff for operation via local operation or handheld terminal 375 Field
18 ff for operation via operating tool.
!
Note!
Locking by password has the highest priority and can only be disabled via the SAFETY LOCK and SAFETY
PASSWORD parameters.
Unlocking
1.
Select the "SAFETY CONFIRM." group. (Menu path: (GROUP SELECTION
→
) OPERATING MENU
→
SAFETY CONFIRM.).
2.
Select the "Unlock" option via the SAFETY LOCK parameter.
3.
Enter the password "7452" via the SAFETY PASSWORD parameter. If the password entered is correct,
the SAFETY LOCK or SAFETY LOCKSTATE parameter displays the status "Unlocked".
Standard device configuration
If you are using the "Standard device configuration" method (
26), the device has to be locked via the
software and/or the hardware.
→
Operating Instructions BA332P, Section 5.9 "Locking/Unlocking
operation".