The condition that the value for PRESSURE FULL – PRESSURE EMPTY must not drop below the minimum span (1 % of
sensor measuring range) is not met (Point
➂
). The "Increased security during parameter entry" method cannot be
performed for the device without a correction.
Point
➂
:
The value for PRESSURE FULL – PRESSURE EMPTY
must not fall below the minimum span (1 % of sensor measuring
range).
!
Note!
• If the device has assumed a fault condition, i.e. an alarm is output and the current output assumes the set
value, the cause of the fault must first be eliminated.
• When operating via DTM, locking via the SAFETY LOCK menu is only possible in the online mode.
• The sensor can only be recalibrated by Hauser Service. As the parameters for a sensor recalibration
are not reset with the "7864" reset code, the parameters have to be checked prior to locking via the SAFETY
CONFIRM. menu.
0 mbar
0 m
0.032 m
0.08 m
20 mA
4 mA
3.2 mbar
I
H
p
3
Pressure value
for 20 mA =
8 mbar
EMPTY PRESS. FULL PRESS.
EMPTY
CALIB.
FULL
CALIB.
SET LRV
SET URV
Содержание Deltapilot S FMB70