BA00382P/00/EN/13.10
71123275

Valid from software version:
01.00.zz

Operating Instructions

Cerabar M

PMC51, PMP51, PMP55

Deltabar M 

PMD55

Deltapilot M  FMB50/51/52/53

Process pressure / Differential pressure, Flow / Hydrostatic 

Deltapilot M

Deltabar M

Cerabar M

Содержание Deltapilot M FMB50

Страница 1: ...275 Valid from software version 01 00 zz Operating Instructions Cerabar M PMC51 PMP51 PMP55 Deltabar M PMD55 Deltapilot M FMB50 51 52 53 Process pressure Differential pressure Flow Hydrostatic Deltapi...

Страница 2: ...the Internet See www endress com Download Operating Instruction BA00382P Identification Installation Wiring Operation Commissioning Examples of configuration Description of parameters Maintenance Tro...

Страница 3: ...n optional 36 4 5 Post connection check 37 5 Operation 38 5 1 Operating options 38 5 2 Operation without operating menu 39 5 3 Operation with an operating menu 41 6 Commissioning 51 6 1 Function check...

Страница 4: ...sts authorized to perform such work by the facility s owner operator The specialist staff must have read and understood these Operating Instructions and must follow the instructions they contain Modif...

Страница 5: ...rdous areas Devices used in hazardous areas must possess an appropriate type of protection Safe area non hazardous area This symbol is used in the drawings of these Operating Instructions to indicate...

Страница 6: ...dent for re orders 4 Serial number for identification 5 MWP maximum working pressure 6 Electronic version output signal 7 Min max span 8 Nominal measuring range 9 Supply voltage 10 Length data 11 ID n...

Страница 7: ...onic version output signal 9 Cable entry 10 Supply voltage 11 Min max span 12 Wetted materials 13 ID number of notified body with regard to ATEX optional 14 ID number of notified body with regard to P...

Страница 8: ...truction KA01030P Cerabar M KA01027P Deltabar M KA01033P Deltapilot M Final inspection report Additional Safety Instructions for ATEX IECEx and NEPSI devices Optional factory calibration form test cer...

Страница 9: ...atches your order 3 1 2 Storage The device must be stored in a dry clean area and protected against damage from impact EN 837 2 Storage temperature range See Technical Information for Cerabar M TI0043...

Страница 10: ...heated Cerabar M is cooled during the cleaning process e g by cold water a vacuum develops for a short time whereby moisture can penetrate the sensor through the pressure compensation 1 If this is the...

Страница 11: ...ped siphon 4 Circular siphon Mount Cerabar M with siphon above the tapping point Fill the siphon with liquid before commissioning The siphon reduces the temperature to almost the ambient temperature P...

Страница 12: ...depending on the type of diaphragm seal A diaphragm seal and the pressure transmitter together form a closed oil filled calibrated system The fill fluid hole is sealed and may not be opened Do not cl...

Страница 13: ...nt of constant extreme medium temperatures which lead to the maximum permissible electronics temperature of 85 C 185 F being exceeded To minimize the influence of rising heat Endress Hauser recommends...

Страница 14: ...ulated up to a certain height The maximum permitted insulation height is indicated on the devices and applies to an insulation material with a heat conductivity 0 04 W m x K and to the maximum permitt...

Страница 15: ...nstalling on pipes or walls for pipes from 1 1 4 up to 2 diameter P01 xMx5xxxx 06 xx xx xx 001 Please note the following when mounting Devices with capillary tubes mount capillaries with a bending rad...

Страница 16: ...Housing mounted with housing adapter included 7 Mounting bracket provided suitable for pipe and wall mounting for pipes from 1 1 4 up to 2 diameter Assembly and mounting 1 Insert the connector item 4...

Страница 17: ...with a sealing ball and lock screw Once the diaphragm seal has been filled the device display should not exceed 10 of the full scale value of the cell measuring range at the zero point The internal pr...

Страница 18: ...y commissioning installation and maintenance without interrupting the process When routing the impulse piping outdoors ensure that sufficient anti freeze protection is used e g by using pipe heat trac...

Страница 19: ...ame distance to the Deltabar M Prior to commissioning fill the impulse piping to the height of the condensate traps Flow measurement in liquids P01 PMD55xxx 11 xx xx xx 002 Measuring layout for flow m...

Страница 20: ...ic pressure When measuring in media with solid parts such as dirty liquids installing separators and drain valves is useful for capturing and removing sediment Level measurement in a closed container...

Страница 21: ...off valves 3 Deltabar M 4 Separator 5 Drain valves 6 Three valve manifold Mount the Deltabar M below the lower measuring connection so that the impulse piping is always filled with liquid Always conne...

Страница 22: ...at the condensate which may be present can run off into the process piping Differential pressure measurement in liquids P01 PMD55xxx 11 xx xx xx 007 Measuring layout for differential pressure measurem...

Страница 23: ...n into account P01 PMD55xxx 06 xx xx xx 004 Mounting bracket for wall and pipe mounting 1 Adaption plate six screws and six washers 2 Mounting bracket bracket for pipe mounting and two nuts Please not...

Страница 24: ...Endress Hauser Typical installation arrangements P01 PMD55xxx 17 xx xx xx 001 A Installation for horizontal impulse pipes H2 version B Installation for vertical impulse pipes V1 version 1 Deltabar M...

Страница 25: ...mounting optional 3 5 1 General installation instructions Note Do not clean or touch process isolating diaphragms with hard or pointed objects The process isolating diaphragm in the rod and cable vers...

Страница 26: ...at any condensate can flow into the process Pressure measurement in steams Mount Deltapilot M with siphon above the tapping point Fill the siphon with liquid before commissioning The siphon reduces th...

Страница 27: ...cable item 1 and the device into account 2 Raise the clamping jaws item 3 Position the extension cable item 1 between the clamping jaws as illustrated in Figure 16 3 Hold the extension cable in positi...

Страница 28: ...ptional Mounting bracket Endress Hauser offers a mounting bracket for installing on pipes or walls for pipes from 1 1 4 up to 2 diameter P01 xMx5xxxx 06 xx xx xx 001 In the case of pipe mounting the n...

Страница 29: ...ded suitable for pipe and wall mounting for pipes from 1 1 4 up to 2 diameter Assembly and mounting 1 Insert the connector item 4 into the corresponding connection jack of the cable item 2 2 Plug the...

Страница 30: ...ft Sealing the probe housing Moisture must not penetrate the housing when mounting the device establishing the electrical connection and during operation Always firmly tighten the housing cover and th...

Страница 31: ...e polarity HF influences and overvoltage peaks are integrated The procedure 1 Check if the supply voltage matches the specified supply voltage on the nameplate 2 Switch off the supply voltage before c...

Страница 32: ...2 Connecting devices with an M12 connector PIN assignment for M12 connector 4 1 3 Devices with 7 8 plug PIN assignment for 7 8 connector 4 1 4 Devices with valve connector P01 xMx5xxxx 04 xx xx xx 00...

Страница 33: ...ponding measured error below 0 1 the current measuring device should exhibit an internal resistance of 0 7 4 2 2 Cable specification Endress Hauser recommends using twisted shielded two wire cables Te...

Страница 34: ...nstallation or Control Drawing ZD supplied EX 4 20 mA min 250 W 1 Copy G H I P Q R S A B C Paste Page On Page Up Delete Bksp Insert J K L T U V _ D E F Hot Key Hot Key M N O W X Y Z 4 7 2 5 8 0 375 FI...

Страница 35: ...th the HART protocol to a computer s USB port This allows remote operation of the transmitter using Endress Hauser s FieldCare operating program Power is supplied to the Commubox through the USB port...

Страница 36: ...length take additional length into account when installing The device is connected as specified in the following graphic For details see TI103R 09 en XA036R 09 a3 and KA161R 09 a6 4 4 1 Wiring P01 xMx...

Страница 37: ...tallation of the device Does the supply voltage match the specifications on the nameplate Is the device connected as per Section 4 1 Are all screws firmly tightened Are the housing covers screwed down...

Страница 38: ...lustration Description Local operation with device display The device is operated using the operating keys on the device display 43 Remote operation via HART handheld terminal The device is operated u...

Страница 39: ...Switch position off on 1 The device is unlocked Parameters relevant to the measured value can be modified The device is locked Parameters relevant to the measured value cannot be modified 2 damping Da...

Страница 40: ...Pressure measuring mode The pressure present is accepted as the lower range value LRV Level measuring mode In pressure level selection Wet calibration mode The pressure present is assigned to the lowe...

Страница 41: ...User role Submenu Meaning use Operator Language Only consists of the Language parameter 000 where the operating language for the device is specified The language can always be changed even if the devi...

Страница 42: ...control system Measurement Contains all the parameters for configuring the measurement Output Contains all the parameters for configuring the current output Communication Contains all the parameters f...

Страница 43: ...the orientation of the device this makes it easy to operate the device and read the measured values P01 Mxxxxxxx 19 xx xx xx 008 Functions 8 digit measured value display including sign and decimal po...

Страница 44: ...tion symbol Data transfer via communication Square root symbol Active measuring mode Flow measurement The root flow signal is used for the current output Error message Out of specification The device...

Страница 45: ...lid Operating key s Meaning O Navigate downwards in the picklist Edit the numerical values and characters within a function S Navigate upwards in the picklist Edit the numerical values and characters...

Страница 46: ...ted as the menu language 2 Exit the edit mode for the parameter with E Local display Operation P01 PMD55xxx 19 xx xx xx 003 The local display shows the parameter to be changed The value highlighted in...

Страница 47: ...mode with or Local display Operation P01 PMD55xxx 19 xx xx xx 009 The pressure for position adjustment is present at the device P01 PMD55xxx 19 xx xx xx 010 Use or to switch to the Confirm option The...

Страница 48: ...offline mode Loading and saving device data upload download Documentation of the measuring point Offline parametrization of transmitters Connection options HART via Commubox FXA195 and the USB port o...

Страница 49: ...ou can only unlock operation again using the operating menu The Operator code parameter is used to lock and unlock the device The release code is defined in the Code definition parameter Parameter nam...

Страница 50: ...ay be changed without a specific unblocking code e g after replacing the electronics Note After a Total reset in FieldCare you have to press the refresh button in order to ensure that the measuring un...

Страница 51: ...Sensor range or F841 Sensor range 1 3 S971 Sensor range Note The device is configured for the Pressure measuring mode as standard The measuring range and the unit in which the measured value is trans...

Страница 52: ...n commissioning 51 Setting lower range value Setting upper range value Pressure is present at device Desired pressure for lower range value is present at device Desired pressure for upper range value...

Страница 53: ...nsor See information on the nameplate Carrying out position adjustment 1 1 Observe warning on commissioning 51 Setting lower pressure value Setting upper pressure value Pressure is present at device D...

Страница 54: ...not have any function in the Flow measuring mode The pressure applied must be within the nominal pressure limits of the sensor See information on the nameplate Carry out position adjustment 1 1 Observ...

Страница 55: ...Possibly a third language language of the manufacturing plant Factory setting English Parameter name Description Measuring mode 005 Selection Menu path Setup Measuring mode Select the measuring mode T...

Страница 56: ...eed not be known Example Measured value 2 2 mbar 0 033 psi You correct the measured value via the Pos zero adjust parameter with the Confirm option This means that you assign the value 0 0 to the pres...

Страница 57: ...re Full pressure Empty height Full height and Set LRV Set URV must be at least 1 apart The value will be rejected and a warning message displayed if the values are too close together 6 5 2 Overview of...

Страница 58: ...jected and a warning message displayed if the values are too close together Further limit values are not checked i e the values entered must be appropriate for the sensor and the measuring task for th...

Страница 59: ...le Select the Empty calib parameter Menu path Setup Extended setup Level Empty calib Enter the level value here 0 m for example The pressure value present is assigned to the lower level value by confi...

Страница 60: ...together Further limit values are not checked i e the values entered must be appropriate for the sensor and the measuring task for the measuring device to be able to measure correctly Due to the orie...

Страница 61: ...ation point via the Full calib parameter here 1000 liters 264 US gal for example Menu path Setup Extended setup Level Full calib 9 Enter the pressure value for the upper calibration point via the Full...

Страница 62: ...he value will be rejected and a warning message displayed if the values are too close together Other limit values are not checked i e the values entered must be appropriate for the sensor and the meas...

Страница 63: ...r the upper calibration point is present at the device here 450 mbar 6 75 psi for example Enter the volume value for the upper calibration point via the Full calib parameter here 1000 liters 264 US ga...

Страница 64: ...uring device to be able to measure correctly Due to the orientation of the device there may be pressure shifts in the measured value i e when the container is empty or partly filled the measured value...

Страница 65: ...ib parameter here 1000 liters 264 US gal for example Menu path Setup Extended setup Level Full calib 10 Enter the height value for the upper calibration point via the Full height parameter here 4 5 m...

Страница 66: ...path Setup Ext Setup Level Adjust density 034 e g 1 0 kg l for water Setup Ext Setup Level Process density 035 e g 0 8 kg l for oil Description 1 Select the Level measuring mode via the Measuring mode...

Страница 67: ...ntry option via the Lin mode parameter Menu path Setup Extended setup Linearization Lin mode P01 Mxxxxxxx 19 xx xx xx 006 P01 Mxxxxxxx 05 xx xx xx 015 2 Select the volume mass unit via the Unit after...

Страница 68: ...signed for this In doing so you gain an overview of the selected linearization even while making the entry Additionally it is possible to call up pre programmed tank shapes Note The linearization tabl...

Страница 69: ...rise continuously The Level operating mode has been selected Note For a description of the parameters mentioned Chap 10 2 Description of parameters Description 1 Select the Semi auto entry option via...

Страница 70: ...xxxxxx 05 xx xx xx 016 Fig 37 Semi automatic entry of the linearization table The actual level is displayed via the X value parameter Menu path Setup Extended setup Linearization X value Using the Y v...

Страница 71: ...how to perform position adjustment see 56 Description 1 Select the Pressure measuring mode via the Measuring mode parameter Menu path Setup Measuring mode P01 xxxxxxxx 05 xx xx xx 010 Fig 38 Calibrat...

Страница 72: ...ect the Pressure measuring mode via the Measuring mode parameter Menu path Setup Measuring mode 3 Select a pressure unit via the Press eng unit parameter here mbar for example Menu path Setup Press en...

Страница 73: ...ameter Menu path Setup Measuring mode 2 Select a pressure unit via the Press eng unit parameter here mbar for example Menu path Setup Press eng unit 3 The Cerabar M Deltapilot M is unpressurized perfo...

Страница 74: ...apilot M is unpressurized perform position adjustment see 56 4 Set the output current to Fixed 4 0mA via the Current mode parameter Menu path Expert Communication HART Config 5 Configure an address 0...

Страница 75: ...flows in 3 Clean impulse piping if necessary 1 by blowing out with compressed air in the case of gases by rinsing out in the case of liquids 1 for arrangement with 5 valves Close 2 and 4 Block off dev...

Страница 76: ...on adjustment 113 Pos zero adjust 007 Selection Position adjustment the pressure difference between zero set point and the measured pressure need not be known Example Measured value 2 2 mbar 0 033 psi...

Страница 77: ...or mass flow Four flow types are available volume flow norm volume flow European norm conditions standard volume flow American standard conditions mass flow and flow in In addition the Deltabar M soft...

Страница 78: ...Open 1 and 5 Blow out rinse out impulse piping Close 1 and 5 Close valves after cleaning 4 Vent device Open 2 and 4 Introduce fluid Close 4 Close low pressure side Open 3 Balance positive and low pres...

Страница 79: ...nt the pressure difference between zero set point and the measured pressure need not be known Example Measured value 2 2 mbar 0 033 psi You correct the measured value via the Pos zero adjust parameter...

Страница 80: ...Open container I Deltabar M II Separator 6 Vent valves on Deltabar M A Shut off valve B Drain valve 2 Fill measuring system with fluid Open A Open shut off valve 3 Vent device Open 6 briefly then clos...

Страница 81: ...Fill measuring system with fluid Close 3 Shut off high pressure side from low pressure side Open A and B Open shut off valves 3 Vent high pressure side empty low pressure side if necessary Open 2 and...

Страница 82: ...with fluid Open A and B Open shut off valves Fill the negative impulse piping to the level of the condensate trap 3 Vent device Open 2 and 4 Introduce fluid Close 4 Close low pressure side Open 3 Bala...

Страница 83: ...height Full height and Set LRV Set URV must be at least 1 apart The value will be rejected and a message output if the values are too close together 6 11 3 Overview of level measurement Measuring task...

Страница 84: ...her Other limit values are not checked i e the values entered must be appropriate for the sensor and the measuring task for the device to be able to measure correctly Description 1 Perform position ze...

Страница 85: ...xxxxxxx 05 xx xx xx 011 Calibration with reference pressure wet calibration 1 See Table Step 7 2 See Table Step 8 8 a The pressure for the upper calibration point is present at the device here 300 mba...

Страница 86: ...part The value will be rejected and a message output if the values are too close together Other limit values are not checked i e the values entered must be appropriate for the sensor and the measuring...

Страница 87: ...point via the Empty pressure parameter 115 here 0 mbar for example Menu path Setup Extended setup Level Empty pressure 9 Enter the volume value for the upper calibration point via the Full calib para...

Страница 88: ...utput if the values are too close together Other limit values are not checked i e the values entered must be appropriate for the sensor and the measuring task for the device to be able to measure corr...

Страница 89: ...xample Menu path Setup Extended setup Level Full calib 10 Enter the volume value for the lower calibration point via the Empty calib parameter 115 here 0 liter for example Menu path Setup Extended set...

Страница 90: ...r limit values are not checked i e the values entered must be appropriate for the sensor and the measuring task for the device to be able to measure correctly Description 1 Perform position zero adjus...

Страница 91: ...ibration 1 See table Step 10 2 See table Step 8 3 See table Step 9 9 a The pressure for the upper calibration point is present at the device here 400 mbar 6 psi for example b Select the Full calib par...

Страница 92: ...EX filter 1 free from contamination P01 xMx5xxxx 17 xx xx xx 000 7 1 Exterior cleaning Please note the following points when cleaning the device The cleaning agents used should not corrode the surface...

Страница 93: ...low pressure present This message normally only appears briefly 1 Check the pressure value 2 Restart the device 3 Perform a reset F002 Sens unknown Sensor does not suit the device electronic sensor na...

Страница 94: ...ing M002 Sens unknown Sensor does not suit the device electronic sensor nameplate Device continues measuring 1 Contact Endress Hauser Service M283 Permanent mem Cause as indicated for F283 Correct mea...

Страница 95: ...c pressure 2 Check sensor range S822 Process temp The temperature measured in the sensor is greater than the upper nominal temperature of the sensor The temperature measured in the sensor is lower tha...

Страница 96: ...ialist personnel or Endress Hauser may repair certified devices Relevant standards national hazardous area regulations and safety instructions and certificates must be observed Only genuine Endress Ha...

Страница 97: ...lows 1 Go to www endress com and select your country 2 Click Instruments 3 Enter the product name into the product name field 4 Select the device 5 Click the Accessories Spare parts tab 6 Select the r...

Страница 98: ...re history Device Date Software version Software modifications Documentation CD ROM Operating Instruction Cerabar 09 2009 01 00 zz Original software Compatible with FieldCare from version 2 02 00 Fiel...

Страница 99: ...lot M 4 20 mA HART Technical data Endress Hauser 99 9 Technical data For the technical data please refer to the Technical Information for Cerabar M TI436P Deltabar M TI434P Deltapilot M TI437P 2 Overv...

Страница 100: ...High pressure side read only 006 183 112 Press eng unit 125 111 Corrected press 172 113 Pos zero adjust Deltabar M and relative pressure sensors Calib offset absolute pressure sensor 007 192 111 111 M...

Страница 101: ...041 117 Edit table 042 117 Tank description 173 117 Tank content 043 117 Flow Flow measuring mode Deltabar M Flow type 044 117 Mass flow unit 045 117 Norm flow unit 046 118 Std flow unit 047 118 Flow...

Страница 102: ...27 Max meas press 074 127 Diagnostic list Diagnostic 1 075 128 Diagnostic 2 076 128 Diagnostic 3 077 128 Diagnostic 4 078 128 Diagnostic 5 079 128 Diagnostic 6 080 128 Diagnostic 7 081 128 Diagnostic...

Страница 103: ...115 129 Sim tank cont 116 130 Sim current 117 130 Sim error no 118 130 Reset Enter reset code 124 110 Expert Direct access 119 108 System Code definition 023 108 Lock switch 120 108 Operator code 021...

Страница 104: ...ress 172 113 Pressure af damp 111 113 Level Level selection 024 114 Output unit 025 114 Height unit 026 114 Calibration mode 027 114 Empty calib Empty calib 028 011 115 Empty pressure Empty pressure r...

Страница 105: ...output Output current read only 054 120 Alarm behavior P 050 120 Alarm cur switch read only 165 120 Output fail mode Output fail mode read only 190 051 120 High alarm curr 052 120 Set min current 053...

Страница 106: ...179 124 HART input unit 156 125 HART input form 157 125 Application Electr delta P 158 125 Fixed ext value 174 125 Totalizer 1 Deltabar M Eng unit totalizer 1 058 059 060 061 126 Totalizer 1 mode 175...

Страница 107: ...gnostic 8 082 128 Diagnostic 9 083 128 Diagnostic 10 084 128 Event logbook Last diag 1 085 128 Last diag 2 086 128 Last diag 3 087 128 Last diag 4 088 128 Last diag 5 089 128 Last diag 6 090 128 Last...

Страница 108: ...n to enter a release code with which the device can be unlocked Options A number between 0 and 9999 Factory setting 0 Lock switch 120 Display Displays the status of DIP switch 1 on the electronic inse...

Страница 109: ...sion 099 Display Displays the ENP version ENP electronic nameplate Electr serial no 121 Display Displays the serial number of the main electronics 11 alphanumeric characters Sensor serial no 122 Displ...

Страница 110: ...lay Displays the status of DIP switch 4 on the electronic insert which is used to define the output characteristics of the current output Display SW setting The output characteristics is defined by th...

Страница 111: ...the Calib offset parameter This means that you are assigning the value 980 0 14 7 psi to the pressure present Measured value after pos zero adjust 980 0 mbar 14 7 psi The current value is also correct...

Страница 112: ...essure side P2 High SW P2 High is switched on Pressure input P2 corresponds to the high pressure side independent of the setting in the High pressure side 006 parameter Factory setting SW setting High...

Страница 113: ...ted press 172 Display Displays the measured pressure after sensor trim and position adjustment Pressure af damp 111 Display Displays the measured pressure after sensor trim position adjustment and dam...

Страница 114: ...describe the measured value This means that the measured value is not converted when a new output unit is selected Example Current measured value 0 3 ft New output unit m New measured value 0 3 m Opti...

Страница 115: ...int container full The unit defined in Output unit must be used Note In the case of wet calibration the level container full must actually be available The associated pressure is then automatically re...

Страница 116: ...verted beforehand Level before lin is output Erase table The existing linearization table is deleted Manual entry sets the table to the edit mode an alarm is output The value pairs of the table X valu...

Страница 117: ...5 via the Line numb parameter Select the Delete point option via the Edit table parameter The 5th point is deleted All of the subsequent points are moved up one number i e following deletion the 6th...

Страница 118: ...splayed with the new unit within a flow type When the flow type is changed conversion is not possible Prerequisite Flow type 044 Volume process cond Options dm3 s dm3 min dm3 h m3 s m3 min m3 h m3 d l...

Страница 119: ...esis between the switch on point and the switch off point is always 1 of the maximum flow value Input range 0 50 of the end flow value t Max flow 009 P01 PMD7xxxx 05 xx xx xx 000 Factory setting 5 of...

Страница 120: ...m current is 3 6 mA regardless of the software setting Output fail mode 190 Selection Select the output fail mode In the event of an alarm the current assumes the current value specified with this par...

Страница 121: ...016 Entry only in pressure measuring mode Set the upper range value reference pressure is present at the device The pressure for the upper current value 20 mA is present at the device With the Confir...

Страница 122: ...he Current option in the Simulation mode parameter 2 Enter the 20 mA value in the Sim current parameter 3 Enter the current value measured with the switching unit in the Curr trim 20mA parameter Input...

Страница 123: ...g data via the HART protocol HART 5 0 master Range 0 to 15 where address 0 calls up the Signaling setting HART 6 0 master range 0 to 63 Factory setting 0 Preamble number 146 Entry Enter the number of...

Страница 124: ...mary value is Secondary val is 149 Display Secondary value Displays the assignment The following process values can be displayed depending on the measuring mode selected Meas pressure Sensor pressure...

Страница 125: ...tting Unknown HART input form 157 Selection Specify the format for displaying the HART input value Options x x default x xx x xxx x xxxx x xxxxx Factory setting x x Parameter name Description Electr d...

Страница 126: ...Volume process cond Factory setting m3 Totalizer 1 mode 175 Define the behavior of the totalizer Options Balanced Integration of all measured flows positive and negative Pos flow only only positive fl...

Страница 127: ...otalizing is continued Hold The totalizer is stopped and keeps its current value Totalizer 2 069 Display Displays the total flow value of totalizer 2 The Totalizer 2overflow 070 parameter displays the...

Страница 128: ...and then starts again at zero Parameter name Description Diagnostic 1 075 Diagnostic 2 076 Diagnostic 3 077 Diagnostic 4 078 Diagnostic 5 079 Diagnostic 6 080 Diagnostic 7 081 Diagnostic 8 082 Diagno...

Страница 129: ...PMD55xxx 05 xx xx en 007 Factory setting None Sim pressure 113 Entry Enter the simulation value See also Simulation mode Prerequisite Simulation mode Pressure Switch on value Current pressure measure...

Страница 130: ...le lin mode and Simulation mode Tank content Sim current 117 Entry Enter the simulation value See also Simulation mode Prerequisite Simulation mode Current value Factory setting Current value of the c...

Страница 131: ...0 034 A1 i EP 0 445 382 B1 US 5 005 421 A1 i EP 0 351 701 B1 EP 0 414 871 B1 EP 1 061 351 B1 US 5 334 344 A1 i EP 0 490 807 B1 US 6 703 943 A1 Deltabar M DE 203 11 320 U1 US 6 631 644 A1 i EP 1 299 70...

Страница 132: ...l pressure measuring mode 52 L Language selection 55 Level measurement 57 83 Level measurement installation 20 Level measurement preparatory steps 80 Linearization 67 Local display 43 Locking operatio...

Страница 133: ...__________________________________________ ______________________________________________________________________________________________________________ We hereby certify that this declaration is fil...

Страница 134: ...www endress com worldwide BA00382P 00 EN 13 10 71123275 CCS FM SGML6 0 71123275...