Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
94
Hauser
STD. FLOW UNIT (660)
Selection
Select standard volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = Gas std. conditions
Options:
• Sm3/s, Sm3/min, Sm3/h, Sm3/day
• SCFS, SCFM, SCFH, SCFD
• User unit,
see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
Sm
3
/s
MASS FLOW UNIT (571)
Selection
Select mass flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = Mass
Options:
• g/s, kg/s, kg/min, kg/min, kg/h
• t/s, t/min, t/h, t/day
• oz/s, oz/min
• lb/s, lb/min, lb/h
• ton/s, ton/min, ton/h, ton/day
• User unit,
see also the following parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
kg/s
CUSTOMER UNIT F (610)
Entry
Enter text (unit) for customer-specific flow unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST.
UNIT FACT. F.
Prerequisite:
• UNIT FLOW = User unit
• NORM FLOW UNIT = User unit
• STD. FLOW UNIT = User unit
• MASS FLOW UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT F parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
Table 14: (GROUP SELECTION
)
OPERATING MENU
SETTINGS
BASIC SETUP "Flow"
Parameter name
Description