Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
80
Hauser
MASS UNIT (709)
Selection
Select mass unit.
Prerequisite:
• LINd. MEASURAND = Pressure and Mass
Options:
• g
• kg
• t
• oz
• lb
• ton
• User unit,
see also the following parameter description for CUSTOMER UNIT M
and CUST. UNIT FACT. M.
Factory setting:
kg
CUSTOMER UNIT M (704)
Entry
Enter text (unit) for customer-specific mass unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST.
UNIT FACT. M.
Prerequisite:
• LINd. MEASURAND = Pressure and Mass,
MASS UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT M parameter. The measured value is displayed with the additional
text "User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. M (703)
Entry
Enter conversion factor for a customer-specific mass unit.
The conversion factor must be entered in relation to the SI unit "kg".
See also
CUSTOMER UNIT M.
Prerequisite:
• LINd. MEASURAND = Pressure and Mass,
MASS UNIT = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 10 kg
i
1 bucket
– Entry CUSTOMER UNIT M: bucket
– Entry CUST. UNIT FACT. M: 0.1
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
HYDR. PRESS MIN. (775)
Entry
Enter the minimum hydrostatic pressure to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum hydrostatic pressure to be
expected, the more accurate the measurement result.
Factory setting:
0.0
Table 12: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL MODE "Pressure Linearized"
Parameter name
Description