Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
72
Hauser
CUST. UNIT FACT. V (607)
Entry
Enter conversion factor for a customer-specific volume unit.
The conversion factor must be entered in relation to the SI unit "m
3
".
See also CUSTOMER UNIT V.
Prerequisite:
• LIN. MEASURAND = Volume, UNIT VOLUME = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 0.01 m3
i
1 bucket
– Entry CUSTOMER UNIT V: bucket
– Entry CUST. UNIT FACT. V: 100
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
MASS UNIT (709)
Selection
Select mass unit.
Prerequisite:
• LIN. MEASURAND = Mass
Options:
• g
• kg
• t
• oz
• lb
• ton
• User unit,
see also the following parameter description for CUSTOMER UNIT M
and CUST. UNIT FACT. M.
Factory setting:
kg
CUSTOMER UNIT M (704)
Entry
Enter text (unit) for customer-specific mass unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST. UNIT FACT. M.
Prerequisite:
• LIN. MEASURAND = Mass, MASS UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT M parameter. The measured value is displayed with the additional
text "User Unit".
Factory setting:
_ _ _ _ _ _ _ _
Table 11: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name