Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
65
EMPTY CALIB. (010)
Entry
Enter level, volume, mass or percentage value for the lower calibration point (container
empty).
The container is either empty or part full. The measured pressure is converted to a height
value using the HEIGHT UNIT, DENSITY UNIT and ADJUST DENSITY parameters and
displayed. Using the parameter EMPTY CALIB., you assign a level, volume, mass or
percentage value to the height value. The unit is selected via the OUTPUT UNIT
parameter (
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
0.0
FULL CALIB. (004)
Entry
Enter level, volume, mass or percentage value for the upper calibration point (container
full).
The container is either completely or almost full. Using the parameters HEIGHT UNIT,
DENSITY UNIT and ADJUST DENSITY, the measured pressure is converted to a height
value and displayed. Using the parameter FULL CALIB., you assign a level, volume, mass
or percentage value to the height value. The unit is selected via the OUTPUT UNIT
parameter (
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
100.0
EMPTY CALIB. (010)
Entry
Enter level, volume, mass or percentage value for the lower calibration point (container
empty).
The values entered for the EMPTY CALIB. and EMPTY HEIGHT parameters form the
height-level value pair for the lower calibration point. The unit is selected via the
OUTPUT UNIT parameter (
Page 64).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
EMPTY HEIGHT (009)
Entry
Height value for the lower calibration point (container empty). The unit is selected via the
HEIGHT UNIT parameter (
Page 64).
See also EMPTY CALIB.
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
Upper range limit (URL) coverted to an height unit
FULL CALIB. (004)
Entry
Enter level, volume, mass or percentage value for the upper calibration point (container
full).
The values entered for the FULL CALIB. and FULL HEIGHT parameters form the height-
level value pair for the upper calibration point. The unit is selected via the OUTPUT UNIT
parameter (
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
100.0
Table 9: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Height"