Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
130
Hauser
P01-xxxxxxxx-19-xx-xx-xx-144
Fig. 47:
SYSTEM 2 group
Table 34: (GROUP SELECTION
) OPERATING MENU
DIAGNOSTICS
USER LIMITS
Parameter name
Description
Pmin ALARM WINDOW
(332)
Entry
Customer-specific process monitoring – enter lower pressure limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 8.1 "Messages", table, Code E730 and
Section 8.2. "Response of outputs to errors".
Factory setting:
Low sensor limit •1.1
(
For the low sensor limit, see PRESS. SENS LOLIM.)
Pmax ALARM WINDOW
(333)
Entry
Customer-specific process monitoring – enter upper pressure limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 8.1 "Messages", table, Code E731 and
Section 8.2. "Response of outputs to errors".
Factory setting:
High sensor limit •1.1
(
For the high sensor limit, see PRESS. SENS HILIM.)
Tmin ALARM WINDOW
(334)
Entry
Customer-specific process monitoring – enter lower temperature limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 8.1 "Messages", table, Code E732 and
Section 8.2. "Response of outputs to errors".
Factory setting:
Lower sensor temperature application limit – 10 K
(
For the lower temperature application limit, see Tmin SENSOR)
Tmax ALARM WINDOW
(335)
Entry
Customer-specific process monitoring – enter upper temperature limit.
You can use the SELECT ALARMTYPE parameter to enter how the device responds if the
operating pressure undershoots the specified value.
See also these Operating Instructions, Section 8.1 "Messages", table, Code E733 and
Section 8.2. "Response of outputs to errors".
Factory setting:
Upper sensor temperature application limit +10 K
(
For the upper temperature application limit, see Tmax SENSOR)
1)
1)
SE
RV
I
C
E
CURR
. T
R
I
M
4
m
A
CURR
. T
R
I
M 2
0
m
A
OFFSET 4
m
A T
R
I
M
OFFSET
2
0
m
A T
R
I
M
S
Y
STE
M 2
TOTA
L
I
Z
E
R
SET
UP
L
ANG
U
AGE
SETTINGS
P
OSITION A
DJU
ST
M
ENT
O
P
E
R
ATING
M
EN
U
G
R
O
UP
SE
L
E
C
TION
M
e
asu
red
va
l
u
e
1) D
i
sp
l
ay v
i
a
o
n
-
s
i
t
e di
sp
l
ay
o
n
l
y