Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
127
HistoROM CONTROL (832)
Selection
For selecting the direction for copying the data.
See also Operating Instructions BA00270P (Deltabar S), BA00271P (Cerabar S) or
BA00332P (Deltapilot S), Section 5.5. "HistoROM
®
/M-DAT (optional)".
Prerequisite:
• A HistoROM
®
/M-DAT is attached to the electronic insert
(HistoROM AVAIL. = yes)
Options:
• Abort
• HistoROM
Device
• Device
HistoROM
Factory setting:
Abort (if HistoROM
®
/M-DAT is connected to the electronic insert)
Table 32: (GROUP SELECTION
) OPERATING MENU
DIAGNOSTICS
SIMULATION
Parameter name
Description
SIMULATION MODE (413)
Selection
Switch on simulation and select simulation type.
Any simulation running is switched off if the measuring mode or level type is changed.
Options
:
• None
• Pressure,
see also this table parameter description for SIM. PRESSURE
• Flow (only differential pressure transmitter),
see also this table parameter
description for SIM. FLOW VALUE
• Level,
see also this table parameter description for SIM. LEVEL
• Tank content,
see also this table parameter description for SIM. TANK CONT.
• Current,
see also this table parameter description for SIM. CURRENT
Note:
The "Flow" measuring mode has to be selected in the LINEAR/SQROOT parameter to
ensure the current output corresponds to the simulated flow value.
• Alarm/warning, ,
see also this table parameter description for SIM. ERROR NO.
P01-xMx7xxxx-05-xx-xx-xx-012
Factory setting:
None
SIM. PRESSURE (414)
Entry
Enter simulation value.
See also SIMULATION MODE.
Prerequisite:
• SIMULATION MODE = Pressure
Factory setting:
Current pressure measured value
SIM. FLOW VALUE (639)
Entry
Enter simulation value.
See also SIMULATION MODE.
Prerequisite:
• MEASURING MODE = Pressure and SIMULATION MODE = Flow
• MEASURING MODE = Flow and SIMULATION MODE = Flow
Table 31: (GROUP SELECTION
) OPERATING MENU
OPERATING
Parameter name
Description
P
PV
Simulation value pressure
Transducer Block
– Simulation value level
– Simulation value tank content
Simulationvalue flow
Sensor
Analog
Input
Block
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim
P
I
Simulation value pressure
– Simulation value level
– Simulation value tank content
Simulationvalue flow
Simulation value
current
Sensor
Current
output
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim