Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
126
Hauser
Table 31: (GROUP SELECTION
) OPERATING MENU
OPERATING
Parameter name
Description
ENTER RESET CODE (047)
Entry
Reset parameters completely or partially to factory values or delivery status.
See also Operating Instructions BA00270P (Deltabar S), BA00271P (Cerabar S) or
BA00332P (Deltapilot S), Section 5.10 "Factory setting" (reset).
Factory setting:
0
OPERATING HOURS (409)
Display
Displays the hours of operation. This parameter cannot be reset.
INSERT PIN NO (048)
Entry
For entering a code to lock or unlock operation.
!
Note!
• The
-symbol on the on-site display indicates that operation is locked. Parameters
which refer to how the display appears, e.g. LANGUAGE and DISPLAY CONTRAST
can still be altered.
• If operation is locked by means of the DIP-switch, you can only unlock operation again
by means of the DIP-switch. If operation is locked by means of the on-site display or
remote operation e.g. FieldCare, you can unlock operation again by means of the on-
site display or using remote operation.
See also Operating Instructions BA00270P (Deltabar S), BA00271P (Cerabar S) or
BA00332P (Deltapilot S), Section 5.9 "Locking/unlocking operation".
Options:
• Lock: enter a number between 0...9999 which is
100.
• Unlock: enter the number 100.
Factory setting:
100
HistoROM AVAIL. (831)
Display
Indicates whether the optional HistoROM®/M-DAT memory module is connected to the
electronic insert.
See also Operating Instructions BA00270P (Deltabar S), BA00271P (Cerabar S) or
BA00332P (Deltapilot S), Section 5.5 "HistoROM
®
/M-DAT (optional)".
Options:
• Yes (HistoROM
®
/M-DAT is attached to the electronic insert)
• No (HistoROM
®
/M-DAT is not attached to the electronic insert)
DOWNLOAD SELECT (014)
Options
Select download function from HistoROM to device. The selection has no effect on an
upload from the device to the HistoROM.
Prerequisite:
• A HistoROM
®
/M-DAT is attached to the electronic insert
(HistoROM AVAIL. = yes)
Options:
• Configuration copy: For this option, all parameters apart from the DEVICE SERIAL No,
DEVICE DESIGN., CUST. TAG NUMBER, LONG TAG NUMBER, ADDITIONAL
INFO., BUS ADDRESS, CURRENT MODE and the parameters of the POSITION
ADJUSTMENT and PROCESS CONNECTION group are overwritten.
• Device replacement: With this option, all parameters except for DEVICE SERIAL No,
DEVICE DESIGN. and the parameters of the POSITION ADJUSTMENT and PROCESS
CONNECTION group are overwritten.
• Electronics replace: With this option, all parameters except for the parameters of the
POSITION ADJUSTMENT group are overwritten.
Factory setting:
Copy config. (if HistoROM
®
/M-DAT is attached to the electronic insert)