Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
102
Hauser
EDITOR TABLE (809)
Selection
Select table.
Prerequisite:
• TABLE SELECTION = editor table
Options:
• New table:
enter new linearisation table.
• Edit measure table:
The measuring table is loaded as an editor table so that changes can be made.
See
also TAB. SELECTION
• Continue edit:
Edit an editor table that already exists.
See also TABLE EDITOR (770)
Factory setting:
New table
EDITOR TABLE
Entry ("Semiautomatic" edit
mode)
– LINE-NUMB (549)
– Y-VAL. (551)
Enter table in the "Semiautomatic" editing mode.
A linearisation table must have at least 2 points and may not have more than 32 points. A
point consists of LINE-NUMB, X-VAL. and Y-VAL. For this editing mode, the container is
filled or emptied in stages.
Example:
Enter point for LEVEL MODE = Pressure Linearized
– LINE-NUMB: confirm value displayed.
– Y-VAL.: depending on the setting in the LINd. MEASURAND parameter, enter the
volume, mass or % value.
– X-VAL.: the hydrostatic pressure present is displayed and saved by confirming the Y-
value.
Example:
Enter point for LEVEL MODE = Height Linearized
– LINE-NUMB: confirm value displayed.
– Y-VAL.: depending on the setting in the COMB. MEASURAND parameter, enter the
volume, mass or % value.
– X-VAL.: the hydrostatic pressure present is measured. Depending on the setting in the
COMB. MEASURAND parameter, the measured pressure is converted to a level unit
or a % and displayed. The value is saved by confirming the Y-value.
Factory setting:
LINE-NUMB = 1, X-VAL. = 0.0, Y-VAL. = 0.0
EDITOR TABLE
Entry ("manual" edit mode)
– LINE-NUMB (549)
– Y-VAL. (551)
– X-VAL. (550)
Enter table in the "manual" editing mode.
A linearisation table must have at least 2 points and may not have more than 32 points. A
point consists of a line number, X-value and Y-value. The container neither has to be
filled nor emptied for this editing mode.
Example:
Enter point for LEVEL MODE = Pressure Linearized
– LINE-NUMB: confirm value displayed.
– X-VAL.: enter pressure value.
– Y-VAL.: depending on the setting in the LINd. MEASURAND parameter, enter the
related volume, mass or % value.
Example:
Enter point for LEVEL MODE = Height Linearized
– LINE-NUMB: confirm value displayed.
– X-VAL.: the hydrostatic pressure present is measured. Depending on the setting in the
COMB. MEASURAND parameter, enter a level value or % value.
– Y-VAL.: depending on the setting in the COMB. MEASURAND parameter, enter the
related volume, mass or % value.
Factory setting:
LINE-NUMB = 1, X-VAL. = 0.0, Y-VAL. = 0.0
Table 18: (GROUP SELECTION
) OPERATING MENU
SETTINGS
LINEARISATION
– on-site operation
Parameter name
Description