Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
101
TANK CONTENT MIN (759)
Entry
Enter the minimum tank contents to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum tank content to be expected, the
more accurate the measurement result.
!
Note!
• If you enter a new value for TANK CONTENT MIN, the value for SET LRV is also
changed. Use SET LRV to assign a %-value, volume value or mass value to the lower
current value. If you want to assign the lower current value a value other than that for
TANK CONTENT MIN, you must enter the desired value for SET LRV. (
SET LRV,
Page 98).
• For the setting LEVEL MODE "Height Linearized" and ASSIGN CURRENT "Linear",
the TANK CONTENT MIN parameter does not affect the SET LRV parameter. (
SET
LRV, Page 98 and ASSIGN CURRENT, Page 113)
Factory setting:
0.0
TANK CONTENT MAX
(713)
Entry
Enter the maximum tank contents to be expected.
The input limits for the subsequent calibration (editing limits) are derived from the value
entered. The closer the value entered corresponds to the maximum tank content to be
expected, the more accurate the measurement result.
!
Note!
• If you enter a new value for TANK CONTENT MAX, the value for SET URV is also
changed. Use SET URV to assign a %-value, volume value or mass value to the upper
current value. If you want to assign the upper current value a value other than that for
TANK CONTENT MAX, you must enter the desired value for SET URV. (
SET URV,
Page 98.)
• For the setting LEVEL MODE "Height Linearized" and ASSIGN CURRENT "Linear",
the TANK CONTENT MAX parameter does not affect the SET URV parameter. (
SET URV, Page 98 and ASSIGN CURRENT, Page 113)
Factory setting:
100.0
TABLE SELECTION (808)
Selection
Select table.
The device works with a measuring and an editor table. The measuring table is used to
calculate the measured value. To make sure measuring also runs properly when entering
a new table, there is another table, the editor table, for entering new values.
Options:
• View meas. table
• Editor table
Factory setting:
View meas. table
LIN. EDIT MODE (397)
Selection
Select the entry mode for the linearisation table.
Prerequisite:
• TABLE SELECTION = Editor table
Options:
• Manual:
the container neither has to be filled nor emptied for this entry mode. Enter the value
pairs for the linearisation table.
• Semiautomatic: the container is filled or emptied in stages in this entry mode. The
device automatically records the hydrostatic pressure. The associated volume, mass or
%-value is entered.
Factory setting:
Manual
Table 18: (GROUP SELECTION
) OPERATING MENU
SETTINGS
LINEARISATION
– on-site operation
Parameter name
Description