Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Commissioning
Hauser
85
7.10.3 Configurable area
The event categories can be individually defined for the following events - irrespective of the
event group to which they are assigned in the factory setting:
•
115
: Sensor overpressure
•
120:
Sensor low pressure
•
715:
Sensor over temperature
•
717:
Transmitter over temperature
•
718:
Transmitter under temperature
•
720:
Sensor under temperature
•
726:
Sensor temperature error-overrange
•
727:
Sensor pressure error-overrange
•
730:
LRV user limits exceeded
•
731:
URV user limits exceeded
•
732:
LRV-Temp. user limits exceeded
•
733:
URV-Temp. user limits exceeded
•
740:
Calculation Overflow, bad configuration
To change the event category, the event must first be assigned to one of the bits 1 to 15. The
FF912ConfigArea_1
to
FF912ConfigArea_15
parameters in the
DIAGNOSTIC
(TRDDIAG)
Block are used for this purpose. The appropriate bit can then be set from
0
to
1
in the desired assignment parameter.
Example
Error
115 "Sensor overpressure"
should no longer be categorized as
Out of Specification
(S)
, and should be categorized as
Function (C)
instead.
1. In the FieldCare navigation window navigate to
Expert
Field Device Diagnostic
Configuration
.