Description of device parameters
Deltabar FMD71, FMD72
50
Description
Switching burst mode on and off.
Options
• On
• Off
Factory setting
Off
Burst Option (143)
Navigation
Expert → Communication → HART config → Burst Option (143)
Write permission
Service engineers/Expert
Description
You can use this parameter to define which command is sent to the master.
Options
• 1 (HART command 1)
• 2 (HART command 2)
• 3 (HART command 3)
• 9 (HART command 9)
Default output: Meas.Diff.Press. (020), Meas. Press.HP (281), Sensor Press. HP (109)
and Sensor Temp. HP (110)
• 33 (HART command 33)
Default output: Meas.Diff.Press. (020), Meas. Press.HP (281), Sensor Press. HP (109)
and Sensor Temp. HP (110)
Factory setting
1 (HART command 1)
Current Mode (144)
Navigation
Expert → Communication → HART config → Current Mode (144)
Write permission
Service engineers/Expert
Description
Configure current mode for HART communication.
Options
• Signaling
Measured value transmission by the current value
• Fixed Fixed current 4.0 mA (multidrop mode)
(Measured value transmission via HART digital communication only)
Factory setting
Signaling
Bus Address (145)
Navigation
Expert → Communication → HART config → Bus Address (145)