Description of device parameters
Deltabar FMD71, FMD72
48
Description
Enter the pressure value for the lower point (4 mA) of the current partial regression lines.
Using this parameter and "Curr. Trim 20 mA", you can adapt the current output to the
transmission conditions.
Options
Carry out the current trim for the lower point as follows.
• In the "Simulation Mode" parameter, select the "Current" option.
• In the "Sim current" parameter, configure the "4 mA value".
• Enter the current value measured using the switching unit in the "Curr. trim 4mA"
parameter.
Input range
Measured current ±0.2 mA
Factory setting
4 mA
Curr. trim 20mA (136)
Navigation
Expert → Output → Current output → Curr. trim 20mA (136)
Write permission
Service engineers/Expert
Description
Enter the pressure value for the upper point (20 mA) of the current partial regression
lines. Using this parameter and "Curr. Trim 4 mA", you can adapt the current output to the
transmission conditions.
Options
Carry out the current trim for the upper point as follows:
• In the "Simulation Mode" parameter, select the "Current" option.
• In the "Sim current" parameter, configure the value "20 mA".
• Enter the current value measured using the switching unit in the "Curr. trim 20mA"
parameter.
Input range
Measured current ±1 mA
Factory setting
20 mA
Offset trim 4mA (137)
Navigation
Expert → Output → Current output → Offset trim 4mA (137)
Write permission
Service engineers/Expert
Description
Display/enter the difference between 4 mA and the value entered for the parameter "Curr.
trim 4mA".
Factory setting
0
Offset trim 20mA (138)