Description of device parameters
Deltabar FMD71, FMD72
34
Options
• %
• cm, dm, m, mm
• hl
• in
3
, ft
3
, m
3
,
• l
• in, ft
• kg, t
• lb
• gal
• Igal
Factory setting
%
Line numb. (039)
Navigation
Expert → Measurement → Linearization → Line-numb. (039)
Write permission
Operators/Service engineers/Expert
Description
Enter the number of the current point in the table. The subsequent entries in "X-val." and
"Y-val." refer to this point.
Input range
1...32
X-value (040)/(123)/(193)
Navigation
Expert → Measurement → Linearization → X-value (040)/(123)/(193)
Write permission
Operators/Service engineers/Expert
Description
Enter the X-value (level before linearization) for the specific point in the table and confirm.
Note
• If "Lin. mode" = "Manual", the level value must be entered.
• If "Lin. mode" = "Semiautomatic", the level value is displayed and has to be confirmed by
entering the paired Y-val.
Y-val (041)/(194)
Navigation
Expert → Measurement → Linearization → Y-val (041)/(194)
Write permission
Operators/Service engineers/Expert
Description
Enter the Y-val (value after linearization) for the specific point in the table. The unit is
determined by "Unit after lin."
Note
The linearization table must be monotonic (increasing or decreasing).