Description of device parameters
Deltabar FMD71, FMD72
32
Navigation
Expert → Measurement → Level → Full Pressure (032)/(187)
Write permission
Operators/Service engineers/Expert
Description
Enter the pressure value for the upper calibration point (vessel full). See also "Full Calib.".
Prerequisite
• "Level Selection" = In pressure
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting
URL of the sensor module
Full height (033)/(188)
Navigation
Expert → Measurement → Level → Full height (033)/(188)
Write permission
Operators/Service engineers/Expert
Description
Enter the height value for the upper calibration point (vessel full). The unit is selected via
the "Height unit" parameter.
Prerequisite
• "Level Selection" = "In height"
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting
URL is converted to a level unit
Adjust density (034)
Navigation
Expert → Measurement → Level → Adjust Density (034)
Write permission
Operators/Service engineers/Expert
Description
Enter the density of the medium used to perform the calibration. The measured pressure is
converted to a height using the "Height unit" and "Adjust Density" parameters.
Factory setting
1.0
Process Density (035)
Navigation
Expert → Measurement → Level → Process Density (035)
Write permission
Operators/Service engineers/Expert