Cerabar M, Deltapilot M
About this document
Hauser
7
1.3
Terms and abbreviations
URL
OPL
MWP
LRL
0
p
LRV
URV
1
2
3
4
A0029505
Item Term/abbrevia-
tion
Explanation
1
OPL
OPL: The OPL (over pressure limit = sensor overload limit) for the measuring device depends on the lowest-rated ele-
ment, with regard to pressure, of the selected components, i.e., the process connection has to be taken into consideration
in addition to the measuring cell. Observe pressure-temperature dependency.
2
MWP
MWP: The MWP (maximum working pressure) for the sensors depends on the lowest-rated element, with regard to
pressure, of the selected components, i.e., the process connection has to be taken into consideration in addition to the
measuring cell. Observe pressure-temperature dependency. The MWP may be applied at the device for an unlimited
period of time. The MWP can be found on the nameplate.
3
Maximum sensor
measuring range
Span between LRL and URL
This sensor measuring range is equivalent to the maximum calibratable/adjustable span.
4
Calibrated/adjusted
span
Span between LRV and URV
Factory setting: 0 to URL
Other calibrated spans can be ordered as customized spans.
p
-
Pressure
-
LRL
Lower range limit
-
URL
Upper range limit
-
LRV
Lower range value
-
URV
Upper range value
-
TD (Turn down)
Turn down
Example - see the following section.