Cerabar M, Deltapilot M
Operation
Hauser
37
6.3.2
Structure of the operating menu
User
role
Sub-
menu
Meaning/use
Opera-
tor
Lan-
guage
Only consists of the "Language" parameter (000) where the operating language for the
device is specified.
The language can always be changed even if the device is locked.
Opera-
tor
Display/
operat.
Contains parameters that are needed to configure the measured value display (selecting
the values displayed, display format, etc.). With this submenu, users can change the meas-
ured value display without affecting the actual measurement.
Mainte-
nance
Setup
Contains all the parameters that are needed to commission measuring operations. This
submenu has the following structure:
•
Standard setup parameters
A wide range of parameters, which can be used to configure a typical application, is
available at the start. The measuring mode selected determines which parameters are
available.
After making settings for all these parameters, the measuring operation should be com-
pletely configured in the majority of cases.
•
"Extended setup" submenu
The "Extended setup" submenu contains additional parameters for more accurate config-
uration of the measurement, for converting the measured value and for scaling the out-
put signal.
This menu is split into additional submenus depending on the measuring mode selec-
ted.
Mainte-
nance
Diagno-
sis
Contains all the parameters that are needed to detect and analyze operating errors. This
submenu has the following structure:
•
Diagnostic list
Contains up to 10 currently active error messages.
•
Event logbook
Contains the last 10 error messages (no longer active).
•
Instrument info
Contains information for identifying the device.
•
Measured values
Contains all the current measured values.
•
Simulation
Is used to simulate pressure, level, current and alarm/warning.
•
Enter reset code
Expert
Expert
Contains all the parameters of the device (including those already in one of the other sub-
menus). The "Expert" submenu is structured by the function blocks of the device. It thus
contains the following submenus:
•
System
Contains all the device parameters that do not pertain either to the measurement or to
integration into a control system.
•
Measurement
Contains all the parameters for configuring the measurement.
•
Output
Contains all the parameters for configuring the current output.
•
Communication
Contains all the parameters for configuring the communication interface.
•
Application
Contains all the parameters for configuring the functions that go beyond the actual
measurement.
•
Diagnosis
Contains all the parameters that are needed to detect and analyze operating errors.
For an overview of the entire operating menu .
6.4
Operation with device display (optional)
A 4-line liquid crystal display (LCD) is used for display and operation. The local display
shows measured values, dialog texts, fault messages and notice messages. For easy opera-
tion the display can be taken out of the housing (see figure steps 1 to 3). It is connected to
the device via a 90 mm (3.54 in) long cable. The display of the device can be turned in 90°