Commissioning
ASP station 2000 peristaltic
106
Hauser
Synchronisation
Menu structure:
Fig. 51:
Synchronisation menu structure
You can use synchronisation to assign specific filling times to specific bottles. In this way you could
fill bottle 1 between 00:00 and 02:00 and bottle 2 between 02:00 and 04:00 etc. For this, you have
the following options:
• AUT button: the sampling and bottle change times are not synchronised.
• Synchronisation TIME: sampling starts with the first bottle. The change to the next bottles is
synchronised. For example, a time of 2:00 hours was set for the bottle change. The point 00:00
(= at a full hour) was set for the synchronisation. If the programme is started at 05:20, bottle 1 is
filled. The system then changes to bottle 2 at 06:00.
• Synchronisation TIME+BOT.: each bottle is allocated a specific filling time.
Example: 00:00-02:00: bottle 1; 02:00-04:00: bottle 2; 04:00-06:00: bottle 3, etc.
For example if you start the programme at 10:00, the unit will start filling bottle 6.
6.4.6
Creating switching programmes
Sample mode
Menu structure:
Fig. 52:
Sample mode menu structure
In the switching programmes, like in the main programmes, you can trigger sampling by time,
volume, flow or an external signal.