background image

ENDA EUP1122 RAIL MOUNTED UNIVERSAL PID CONTROLLER

Thank you for choosing 

ENDA EUP1122

 Rail mounted PID universal controller.

Max. 2000m.

80% Relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C.

0 ... +50

 

°C/-25 ... +70°C (with no icing)

.

According to EN 60529 IP20.

24 VDC 20%.

Max.

 

5

VA

.

1.5

mm²’

 

screw-terminal connections.

EN 61326-1: 2013
EN 61010-1: 2010 ( Pollution degree 2, overvoltage category II )

Max. 

100Ω Ohm

. for thermocouple. Max. 20

Ω

 ohm. For three-wire Pt100.

Rail - mounted box according to DIN 43 700.
W29xH90xD64mm
Approx. 200g (after packing)
Self extinguishing plastics used.

FLASH Memory (minimum 20 years).

Read this document carefully before using this device. The guarantee will be expired by damaging of the device if you don't 
attend to the directions in the user manual. Also we don't accept any compensations for personal injury, material damage or 
capital disadvantages.

 Height

Ambient/storage temperature

Max. Relative humidity

Protection rating

ENVIRONMENTAL CONDITIONS

ELECTRICAL CHARACTERISTICS

 

Supply
Power Consumption

 

Wiring

 EMC

Safety Requirements

Line Resistance
Data Retention

HOUSING

Housing Type
Dimensions

 Weight

Enclosure Material

DIN Rail Mounting.
Selectable Dual-set value.
PT100, J, K, L, T, S, R sensor types can be used.
0-20mA, 4-20mA, 0-10V, 2-10V, 0-25mV and 0-50mV input selections.
Programmable D1 and D2 digital contact input.

Control outputs can be disabled (Applied for measurement use).
Manual control for C/A2 or ALN/SSR outputs.
Soft-Start feature.
Communication via RS485 Modbus protocol.
Analogue, SSR or Relay output control selection.
0-20mA, 4-20mA, 0-10V and 2-10V Analogue Output Control selection.
C/A2 Relay output can be set as secondary Alarm or Temperature Control output.
Heating/Cooling control selection.
Zero point input shift (Offset feature for input).
In case of sensor failure, relay positions can be selected or periodic operation can be performed.
Can be programmed via Modbus.
Up to 16 steps profile controlling feature.
Contact output triggering feature at profile steps.
Timer or Thermostat feature can be used during profile controlling.
Modbus addressing, baud rate settings or default settings can be applied via DIP Switch.
Heating error monitoring feature.
Update featutre via RS485.
CE Marked according to European Norms.

Auto calculation for PID parameters (SELF TUNE).

Selftune  for  automatic  PID  calculation  or 
manually enter PID parameters if known.

Programmable 1st.  control key input.

Relay : 250V AC, 5A (for resistive load), NO (Control or Alarm2 Output selection).

OUTPUTS

Single set-point and alarm control.
On-Off / P, PI, PD, PID (selectable).
14 bits.

Adjustable between 0.0 and 100.0 minutes.
Adjustable between 0.00 and 25.00 minutes.

100ms (Minimum).
Adjustable between 0% and 100%. If Pb=0%, On-Off control is selected.

CONTROL

Control Type
Control Algorithm
A/D Converter

Integral Time

Derivative Time

Sampling Time
Proportional Band

Adjustable between 1 and 50°C/F.
The ratio of power at the setpoint value can be set between 0% and 100%.

Adjustable between 1 and 125 seconds.

Hysteresis
Output Power

Control Period

ORDER CODE  :  EUP1122

Programmable 2nd. control key input.

D2 Dry Contact Input

INPUTS

D1 Dry Contact Input

ERR.

ANL/
SSR

2

1

3

4

5

6

7

10

8

11

9

12

ENDA

EUP1122

C/A2

D1

D2

RX

TX

A1

+

-

-

+24V

GND

B-

A+

RS485

COM

+

KEEP AWAY device from exposed to corrosive, volatile and flammable gases or 
liquids and DO NOT USE the device in similar hazardous locations.

Relay : 250V AC, 5A (for resistive load), NO+NC (Alarm1 Output selection).
Used for 0-20mA, 4-20mA, 0-10V, 2-10V Analog output and SSR.
Maximum load resistance is 600

Ω

 Ohm. on mA output and SSR mode. Source resistance is 500

Ω

 Ohm. for V output.

Without load 30.000.000 switching; 250V AC, 5A (resistive load) 300.000 switching.

Life Expectancy for Relay

C/A2 Output

A1 Output

ANL/SSR Control Outputs

Avoid any liquid contact when the device is switched on.
DO NOT clean the device with solvent (thinner, gasoline, acid etc.) and / or abrasive cleaning agents.

EUP1122-EN-01-220120

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:18

ENDA

TM

1

/

8

Содержание EUP1122

Страница 1: ...act output triggering feature at profile steps Timer or Thermostat feature can be used during profile controlling Modbus addressing baud rate settings or default settings can be applied via DIP Switch...

Страница 2: ...Error codes 0 No Error 1 2 3 Upper scale 4 No communication with the sensor 5 Short circuit Lower scale Heater Heating output error I2 1 Sensor short circuited or temperature too low Err Led 60ms 186...

Страница 3: ...START START Time Themperature Time Time PH2 PH4 PH4 PH4 PH4 PH4 PH2 Themperature Fig 3 PROFILE CONTROL OUTPUT SAMPLES PH1 1 PH1 1 PC35 1 PC35 0 PH3 PH3 PC33 1 PC33 1 START START PH2 PH2 PH4 PH4 PH4 P...

Страница 4: ...0 0 minute Control output derivative time Adjustable between 0 01 and 10 00 minute Alarm1 output integral time Adjustable between 0 1 and 100 0 minute Alarm1 output derivative time Adjustable between...

Страница 5: ...ters continue Analog output maximum out percentage Offset value Function control parameter 23040d 5A00h Self tune stops when this value is entered 23041d 5A01h Self tune starts when this value is ente...

Страница 6: ...usted between H2 and H3 parameter 3rd Time value can be set from 0 to 9999 seconds or minutes changes with the depending on PH0 parameter 4th Step target temperature set value can be adjusted between...

Страница 7: ...rol is done with the value of the proportional control Alarm1 condition 0 Alarm is ON at below setpoint value 1 Alarm is OFF at above setpoint value Alarm1 output status in case of probe failure 0 OFF...

Страница 8: ...rform for any reason operating error occurs EUP1122 realizes error and sends error message Most significant bit of function is changed 1 to indicate error in error message by EUP1122 Error code is sen...

Отзывы: