ENVIRONMENTAL CONDITIONS

Ambient/storage temperature

Relative humidity

Pollution degree

Overvoltage category

Altitude

Protection

OUTPUT

INPUT

GENERAL

ERPA1-240-F

40

180 - 280

150
400

1,6

5

880

50 - 60

>0,75

160

0/4-20mA, 0/1-5V DC, 0/2-10V DC or ~ 10k potentiometer. (Device may be damaged at 12V DC and above voltages).

0,2mA (for mA input),  0,08V (for V input).

0,18mA (for mA input),  0,075V (for V input).

15ms.

100  (for mA input),  10k (for V input).

Ω

Protection feature for reverse connection is available.

ERPA1-xxx-F-xx
90-250V AC, 50/60Hz.
W46 x H110 x D117mm (for ERPA1-x40-F and ERPA1-550-F) , W79 x H120 x D132mm (for ERPA1-570-F).
Approx. 450g (for ERPA1-x40-F and ERPA1-550-F) , Approx. 550g (for ERPA1-570-F) (boxed).
2500 Vrms between I/O terminals for 1 min.
For power line 16mm² cable (with 25mm² cable terminal) cable, for signal line can be connected 4mm² cable.
Max. 1,2Nm.
EN 60947-4-3
Rail mountable (EN60715,TH35 or G-32).
Self extinguishing plastics (According to EN 60695-11-10 V-O).
Fan is controlled with thermostat and works at temperatures over 50°C.

ERPA1-440-F

40

180 - 480

110
290

1,8

8

610

50 - 60

>0,75

200

ERPA1-550-F

50

180
270

10

720

300

180 - 500

1,8

50 - 60

>0,75

3A, 250V AC, NO or NC can be selected by program.

ERPA1-570-F

70

400
600

15

4000

400

Order Code

Load Current, AC51/25ºC (Arms)

Load Voltage (Vrms)

Overload Current t=1s/25°C (Arms)

Non rep. Surge current/25°C (Arms)

On-state Voltage Drop (Vrms)

Leakage Current (mArms)

I²t for Fusing t=10ms (A²s)

Frequency (Hz)

Power Factor (Cos )

Φ

Minimum Operating Current (mArms)

Alarm Output

Input Signal

Transmission Signal

Drop-out Signal

Turn-on Time

Dynamic Input Impedance

Protection

Order code
Power supply
Dimensions
Weight
Isolation Voltage
Connection
Terminal screw torque
Product standard
Mounting
Enclosure material
Fa n (Optional)

ORDER CODE

Thank you for choosing 

eries power regulators.

ENDA ERPA1

 S

ERP  A  1 - 5  50 - F - V - RS

ENDA ERPA Series Power Regulators

1

Product Basic Code

 ERP

Rail Mounted

Fan (*)

Fan                              F

Communication

 (*)

RS485 ModBus         RS
Blank (N/A)                 or

Load Voltage

AC                        A

Number of Pole

           1

Single pole

Load Current

40A  AC                         40
50A  AC                         50
70A  AC                         70

Load Voltage

180 - 280V AC      2
180 - 480V AC      4
180 - 500V AC      5

Please rea this document carefully before using this product. The guarantee will be invalidated if the device is damaged by
not following instructions detailed in the manual. The company shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.

-

A

A

40 -50 -70A AC  oad current.

L

-

V

V

280 -480 -500V AC  oad voltage.

L

-

0/4-20mA, 0/1-5V DC, 0/2-10V DC or 1kΩ ~ 10kΩ  otentiometer input.

P

-

4 Digits LED display.

-

Phase angel or zero-cross controlled.

-

Soft Start or Kick Start feature.

-

Overheat alarm output.

-

Varistor protection for peak voltages.

-

RS485 ModBus  ommunication feature (Optional).

C

CE  arked according to European Norms.

M

-

Optional features should

be specified at order.

 Do not use the device in locations subject to corrosive and flammable gases.

While cleaning the device, solvents (thinner, 

, acid etc.) or corrosive materials must not be used.

gasoline

90% Relative humidity for temperatures up to 20 % °C, decreasing linearly to 50% at 40°C. (Shouldn't be condensation).

-25... +60 °C / -30... +100 °C (Shouldn't be icing and condensation in ambient.)

2
II
Max. 1000m.
IP20 According to EN60529

Vibration

 Control (*)

Vibration Control        V
Blank (N/A)                 or

Содержание ERPA Series

Страница 1: ...um Operating Current mArms Alarm Output Input Signal Transmission Signal Drop out Signal Turn on Time Dynamic Input Impedance Protection Order code Power supply Dimensions Weight Isolation Voltage Connection Terminal screw torque Product standard Mounting Enclosure material Fa n Optional ORDER CODE Thank you for choosing eries power regulators ENDA ERPA1 S ERP A 1 5 50 F V RS ENDA ERPA Series Powe...

Страница 2: ...hile assembling there must be at least 25mm clearance between the devices Load Alarm Out Alarm Out Supply 90 250VAC Supply 90 250VAC 0 4 20mA or 0 10V 0 4 20mA or 0 10V 1k to 10k Ω Ω 1k to 10k Ω Ω Potentiometer Potentiometer 180 280VAC A B COM Rs485 ModBus ENDA ERPA1 POWER REGULATOR SET A B COM Rs485 ModBus ENDA ERPA1 POWER REGULATOR SET L N Load 180 480VAC L2 L1 ERPA1 POWER REGULATOR LOAD 40A 180...

Страница 3: ...ction st ty Display selection in Running Mode disp st ti Alarm relay selection Data menu security parameter A out Communication menu security parameter A cnn A con Control menu security parameter codE Security menu access code is 124 baud d adr Max acceptable value for output Min acceptable value for output ou hi ou lo Modbus speed Modbus address Start duration ou of If parameter is set as only wh...

Страница 4: ...ister address Data Type Data content Parameter Name c typ a lou Err c R W Only Readable R W R W Control selection type 0 Phase angel 1 Zero cross Min acceptable value for output acceptable between and 0 ou hi Output value as percent Alarm relay selection 0 NO 1 NC Alarm control management 0 Returns to Run Mode when error disappeares 1 Remains in Eror Mode when error disappeares Bit Byte Bit Bit 00...

Отзывы: