ENDA
ELC-286RT
ENDA PLC PROGRAMMABLE LOGIC CONTROLOR
USER'S MANUAL
1) To avoid damaging the system, do not connect/disconnect the device when power
is on.
2) Make wiring according to user manual to avoid damaging the system.
3) Do not touch live wires.
4) Make sure the ground connection is wired.
5) CE Market according to European Norms.
ELC-286RT PLC unit has got 8 digital inputs, 2 relay outputs, 4 transistor output, 1 analog
input 1 analog output. I/O capacity can extend to 256 point with expansion modules.
PLC parts and mechanical measurement
1
100Mb Ethernet port
10 DIN Ray installation flange
2
RS485 port
11 Digital input terminals
3
RS232 port
12 IO status LEDs
4
PLC power status LED
13 Analog input/output port
5
PLC error status LED
14 Digital output terminal block
6
Program RUN status LED
15 Label area
7
Reset button
16 DIN Ray installation flange
8
17 Expansion modul connector.
9
Power supply terminal
Techical Specifications
Name
Part
Description
General
Power supply
24VDC, ±15% tolerans
Power consumption
3WMax.
CPU process speed
80ns/command
Program language
Graphical Ladder diagram with EndaSoft software.
Program capacity
48kB (Complied code)
Commands
Logic, mathematical, communication, fast counter and timers, function blocks processes.
Communication
ports
Ethernet port
100MB ethernet port for PC programming and network connections.
RS232
Serial port, MODBUS RTU protocol support.
RS485
Serial port, MODBUS RTU protocol support.
Input/Output
Digital outputs
2 channels 220V 3A relay output, 4 channels pnp 24VDC transistor output, (QP2 and QP4
are high speed output max 100kHz)
Digital inputs
8 channels 24VDC pnp, 5mA connection, Logic 1 for >14VDC, Logic 0 for < 13VDC, IP0
and IP1 are high speed counters.
Analog input
1 channel 0-10VDC, 10bit res.
Analog output
1 channel 0-10VDC 12 bit res.
Memory
Integer registers
1024 signed, registers
Float registers
1024 signed float 32 bit registers
Counters
256 counters 32 bit up/down counter
Timers
128 1ms res., 3 type timers
System registers
128 signed 32 bit
Environmental
conditions
Temperature
-10..+60C (without icing)
Humidity
5..95rH humidity
Do not use the device in locations subject to corrosive or flammable gasses.
Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the
manual. The company shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
TECHNICAL SPECIFICATIONS