background image

ENDA

 

ELC-286RT

ENDA PLC PROGRAMMABLE LOGIC CONTROLOR
USER'S MANUAL 

1) To avoid damaging the system, do not connect/disconnect the device when power 

is on.

2) Make wiring according to user manual to avoid damaging the system. 
3) Do not touch live wires.
4) Make sure the ground connection is wired.
5) CE Market according to European Norms.

ELC-286RT PLC unit has got 8 digital inputs, 2 relay outputs, 4 transistor output, 1 analog 
input  1 analog output. I/O capacity can extend to 256 point with expansion modules. 

PLC parts and mechanical measurement

1

100Mb Ethernet port

10 DIN Ray installation flange

2

RS485 port

11 Digital input terminals

3

RS232 port

12 IO status LEDs

4

PLC power status LED

13 Analog input/output port

5

PLC error status LED 

14 Digital output terminal block

6

Program RUN status LED 

15 Label area 

7

Reset button

16 DIN Ray installation flange

8

17 Expansion modul connector.

9

Power supply terminal

      Techical Specifications

Name

Part

Description

General

Power supply

24VDC, ±15% tolerans

Power consumption

3WMax.

CPU process speed

80ns/command

Program language

Graphical Ladder diagram with EndaSoft software. 

Program capacity

48kB (Complied code)

Commands

Logic, mathematical, communication, fast counter and timers, function blocks processes.

Communication 

ports

Ethernet port

100MB ethernet port for PC programming and network connections. 

RS232

Serial port, MODBUS RTU protocol support. 

RS485

Serial port, MODBUS RTU protocol support.

Input/Output

Digital outputs

2 channels 220V 3A relay output, 4 channels pnp 24VDC transistor output, (QP2 and QP4 
are high speed output max 100kHz)

Digital inputs

8 channels 24VDC pnp, 5mA connection, Logic 1 for >14VDC, Logic 0 for < 13VDC, IP0 
and IP1 are high speed counters.

Analog input

1 channel 0-10VDC, 10bit res.

Analog output

1 channel 0-10VDC 12 bit res.

Memory 

Integer registers

1024 signed, registers

Float registers

1024 signed float 32 bit registers

Counters

256 counters 32 bit up/down counter

Timers

128 1ms res., 3 type timers

System registers

128 signed 32 bit 

Environmental

conditions

Temperature

-10..+60C (without icing)

Humidity

5..95rH humidity

Do not use the device in locations subject to corrosive or flammable gasses.

Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the
manual. The company shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.

 TECHNICAL SPECIFICATIONS