3.3.2.
Installation of cooling accessories
●
Install cooling drain pipe
NOTE:
Edgerack 3P is equipped with automatic evaporating condensate water, which can
be used without a drain pipe during normal operation. For emergency drainage,
the installation of a condensate drain pipe is shown in figure 5-2.
3.3.3.
Installation of air duct
It is recommended that the air duct at the top of the EdgeRack 3P be plumbed into
the main HVAC return.
A flexible tube (5 meter x Φ350 mm) is included.
If there is a request for the long-distance air duct installation, please purchase
it with a diameter of 350 mm from a local supplier.
Below is the installed procedure.
●
Install the air duct mounting flange with the supplied M6x16 combination
screws.
●
Place a duct clamp over the air duct mounting flange.
●
Install the air duct over the mounting flange and tighten the duct clamp.
Figure 3-11 Air duct installation diagram
NOTE: If overhead space is limited, the air duct can be clamped to the
mounting flange before the mounting flange is secured to the top of the cabinet.
23