2.4.
Environmental requirements
2.4.1.
Operating conditions
The installation location for EdgeRack 3P should be easily accessed, away from
heat, direct sunlight, and corrosive gasses. Operating conditions are shown in
Table 2-3.
Table 2-3 Operating conditions
Items
Requirement
Temperature
18
℃~
45
℃
Humidity
20%
~
80%
Altitude
Altitude < 1000 m
,
above 1000 m
derating capacity, power derating 6%
per kilometer
Rated voltage
208~240 V 50/60 Hz
Note
• During operation in high temperature and high humidity environments, there may be
condensation on the external surface of the front glass door. However, it is a normal
phenomenon and doesn’t affect the operations or usage.
•
Derating is required for altitudes above 1000 m. For the UPS, the altitude should be
less than 1500 m. Derating is required for altitudes above 1500 m with reference to
local standards.
2.4.2.
Storage Environment
Table 2-4 Storage Environment
Items
Requirement
Environment
Clean (no dust), good ventilation
Environment Temperature
-40℃
~
+60℃
Environment humidity
5
%
RH
~
95
%
RH without
condensation
11