Check all local codes for requirements, especially for the size and 

type of gas supply line required.

NOTICE

:

 Never use plastic pipe. Check to confirm whether your 

local codes allow copper tubing or galvanized.

NOTICE

Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.

Installing a new Main Gas cock

Each appliance should have its own manual gas cock.
In the state of Massachusetts the gas cock must be a T handle 

type.
A manual main gas cock should be located in the vicinity of the unit. 

Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve  and pipe 

capped or plugged for pressure test. never pressure test with 

appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required by 

the National Fuel Gas Code that a drip line be installed near the gas 

inlet. This should consist of a vertical length of pipe tee connected 

into the gas line that is capped on the bottom in which condensation 

and foreign particles may collect. 
 The use of the following gas connectors is recommended:
—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings

—  ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a flexible 

appliance connector cannot exceed three feet in length.

Figure 2

Pressure testing of the Gas supply system

1.  To check the inlet pressure to the gas valve, a 1/8" (3.175mm) 

N.P.T. plugged tapping, accessible for test gauge connection, must 

be placed immediately upstream of the gas supply connection 

to the appliance.

2.    The appliance and its individual shutoff valve must be disconnected 

from the gas supply piping system during any pressure testing of 

that system at test pressures in excess of 1/2 psig (3.5 kPa).

3.    The appliance must be isolated from the gas supply piping system 

by closing its individual manual shutoff valve during any pressure 

testing of the gas supply piping system at test pressures equal 

to or less than 1/2 psig (3.5 kPa).

attention! 

If one of the procedures results in pressures in excess 

of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will 

result in a hazardous condition.

checking Manifold Pressure 

Natural gas models will have a manifold pressure of approximately 

3.5" w.c. (.871kPa) at the pressure regulator outlet with the inlet 

pressure to the pressure regulator from a minimum of 5.0" w.c. 

(1.120kPa) for the purpose of input adjustment to a maximum of 

10.5" w.c. (2.615kPa). 

Propane gas models will have a manifold pressure approximately 

10.0" w.c. (2.49kPa) at the pressure regulator outlet with the inlet 

pressure to the pressure regulator from a minimum of 11.0" w.c. 

(2.739kPa) for the purpose of input adjustment to a maximum of 

13.0" w.c. (3.237kPa). 

olI

NOTICE

The gas control is equipped with a captured screw type 

pressure test point, therefore it is not necessary to provide a 1/8" 

test point up stream of the control.

GAS SUPPLY

recommended Gas Pipe diameter

Pipe Length

Schedule 40 Pipe

Inside Diameter

Tubing, Type L 

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10 feet

0-3 meters

1/2”

12.7mm

3/8”

9.5mm

1/2”

12.7mm

3/8”

9.5mm

10-40 feet

4-12 meters

1/2”

12.7mm

1/2”

12.7mm

5/8”

15.9mm

1/2”

12.7mm

40-100 feet

13-30 meters

1/2”

12.7mm

1/2”

12.7mm

3/4”

19mm

1/2”

12.7mm

100-150 feet

31-46 meters

3/4”

19mm

1/2”

12.7mm

7/8”

22.2mm

3/4”

19mm

Содержание OLI-24-1

Страница 1: ...red in the vicinity of this or any other ap pliance DANGER CARBON MONOXIDE HAZARD This appliance can produce carbon monoxide which has no odor Using it in an enclosed space can kill you Never use this...

Страница 2: ...Before Fully Installing the Appliance 8 Gas Supply 9 Operation Instructions Flame Appearance 10 OLI 24 30 Lighting Instructions 11 Main Burner Flame Characteristics 12 Cleaning and Servicing 12 Wiring...

Страница 3: ...avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Addresses practices not related to personal...

Страница 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Страница 5: ...h apply to the installation of a vented decorative gas log set in a solid fuel burning fireplace This appliance is only for use with the type of gas indicated on the rating plate Instructions to Insta...

Страница 6: ...NAT For appliances for fixed fuel piping system and equipped with an appliance gas pressure regulator the required mani fold pressure in inches water column 10 for LP and 3 5 NAT For appliances for f...

Страница 7: ...m kg of stored fuel capacity and not less than a total free area of 10 square inches 64 5 sq cm If ventila tion openings at floor level are in a side alll there shall be at least two openings The bott...

Страница 8: ...lid Fuel Burning Fireplaces Model A B C D OLI 24 27 18 34 18 OLI 30 30 18 36 18 The dimensions shown and defined in the fireplace instructions are minimum clearances to maintain in installing this hea...

Страница 9: ...ble by the authority havingjurisdiction ThestateofMassachusettsrequiresthataflexible appliance connector cannot exceed three feet in length Figure 2 Pressure Testing of the Gas Supply System 1 To chec...

Страница 10: ...grate Inspect and clean burner air intake hole Remove lint or particles with brush Failure to keep air intake hole clean will result in sooting and poor combustion ANNUAL CLEANING INSPECTION Refer to...

Страница 11: ...ect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE 1 Locate On Off gas cock and turn cloc...

Страница 12: ...high grade stainless steel to resist rust through In outdoor applications all stainless steel will develop a dull patina and depending on the local environment and on the materials used in the instal...

Страница 13: ...l use if batteries are replaced or if a replacement transmitter is purchased from your dealer or the factory In order for the module to accept the transmitter security code be sure the slide button on...

Страница 14: ...e Holder 4 P245 P265 Orifice LP 4 P301 P209 Orifice NAT 5 R10808 R10808 Air Shutter 6 28739 28740 Burner with Bracket 7 R10814 R10814 Spark Probe 8 28089 28089 Valve Shield 9 R10810 R10810 Gas Valve L...

Страница 15: ...anty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numbe...

Страница 16: ...e must be installed by a qualified installer and operated in accordance with the instructions furnished with the appliance A bill of sale cancelled check or payment record should be kept to verify pur...

Отзывы: