41978-2-0321
Page 45
DVVK-4FV DIRECT VENT TERMINATION KIT (CONT’D)
17. To attach the vent connections at the fireplace, be sure the 7
inch diameter adapter collar has been installed per step 3. Ap-
ply a bead of silicone sealant to the 4 inch diameter flex con
-
nector, then slide the flex pipe adapter collar into the fireplace
flue collar and secure by installing a minimum of two screws
through the flue collar and into the adapter.
See Figure 61.
18. Apply sealant to the 7 inch diameter adapter collar, slide outer
flex vent over the collar, then secure with a 7 inch diameter
band clamp.
See Figure 61.
Figure 61
19. Once the lower connections are made and the flex pipe is
secured with support bands as required (3 feet minimum be-
tween supports) then the roof flashing can be installed.
See
Figure 62.
Figure 62
20. Install the roof flashing, and seal using common constructions
practices.
21. An additional storm collar band is provided in kit that may be
used as an attic insulation shield. The collar can be installed
around the flex pipe (or hard pipe) just above the firestop
thimble. This collar will act as a shield to prevent blown insu-
lation from entering the thimble.
22. To complete the vent installation, install the vent termination
cap to the top of the hard vent pipe assembly. Mate up the
flue and outer telescopes with the hard pipe assembly, then
secure by installing a minimum of two sheet metal screws into
the overlapped flanges of the cap and pipe.
23.
Figure 62
shows a completed installation with components
identified and other installation information such as heights
and clearance to combustibles.