Page 30
Installation and Operation Manual - Gateway 3500
ENGLISH
8.1 Clearances
APPLIANCE CLEARANCES WITH SINGLE
WALL PIPE CONNECTOR
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada
USA
Canada
USA
A
13
¼
" (337 mm)
13" (330 mm)
A
7" (178 mm)
7" (178 mm)
B
14" (356 mm)
14" (356 mm)
B
14" (356 mm)
14" (356 mm)
C
7
¼
" (184 mm)
7
¼
" (184 mm)
C
7" (178 mm)
7" (178 mm)
If the above clearances are met, then the distances measured from the flue outlet will be:
DISTANCES
13
FROM PIPE CONNECTOR
WITH SINGLE WALL PIPE CONNECTOR
DISTANCES
13
FROM PIPE CONNECTOR
WITH DOUBLE WALL PIPE CONNECTOR
Canada
USA
Canada
USA
D
18" (457 mm)
17 ¾" (451 mm)
D
11 ¾" (298 mm)
11 ¾" (298 mm)
E
24
⅞
" (632 mm)
24
⅞
" (632 mm)
E
24
⅞
" (632 mm)
24
⅞
" (632 mm)
F
18" (457 mm)
18" (457 mm)
F
17 ¾" (451 mm)
17 ¾" (451 mm)
8.1.1 With Heat Shield AC02710 or AC02762
14
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
DISTANCES13 FROM DOUBLE WALL PIPE
CONNECTOR
Canada
USA
Canada
USA
A
2 ½" (64 mm)
2 ½" (64 mm)
D
7 ¼" (184 mm)
7 ¼" (184 mm)
B
2 ½" (64 mm)
2 ½" (64 mm)
E
13
⅜
" (340 mm)
13
⅜
" (340 mm)
C
2 ½" (64 mm)
2 ½" (64 mm)
F
13 ¼" (337 mm)
13 ¼" (337 mm)
13
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances above
mentioned.
14
Note that to reduce the clearances of an appliance using a single wall pipe connector, the use of a heat shield certified with the single wall pipe
connector to be used as close as 6" from combustible materials must be used. Only in this case, the same clearances as a certified double wall
pipe connector can be used.
Содержание GATEWAY 3500
Страница 2: ......
Страница 6: ...Page 6 Installation and Operation Manual Gateway 3500 ENGLISH CERTIFICATION PLATE...
Страница 35: ...Page 35 Installation and Operation Manual Gateway 3500 ENGLISH...
Страница 62: ...NOTES...
Страница 63: ......