40
Getting Started
CG Drives & Automation, 01-6142-01r0
5.1.2 Toggle loop
Fig. 49 Default toggle loop
To ease commissioning there is a pre-programmed default
toggle loop that can be used to jump between the parameters
described in this guide. Often other settings adjacent to
these entry points should be configured.
•
[211] Language - Select language
•
[221] Motor Volts - Motor configuration
•
[3A11] Drive Conf .- Generic drive configuration
•
[341] Min speed - Speed configuration
•
[3C13] Sensor min – Level sensor configuration
•
[3A21] Overflow low– Configurations of levels (where
to start, stop pumping)
•
[3A31] Level 1 – Reservoir configuration
•
[3A42]LoadMonTune – Option to tune load monitor
during auto tune program
•
[3B31]Act.PumpCln - Option to clean pumps during
auto tune program
•
[3A41] Start AutoT – Start the Auto tune program
5.2
Generic configuration (all
drives)
This section is valid for all drive configurations, stand alone,
master or follower.
5.2.1 Switch on the mains
Once the mains is switched on, the internal fan in the AC
drive will run for 5 seconds (In frame size A3 the fan runs
continuously). The control panel is lighted up and the drive
can be configured.
To change settings use the keys on the control panel as out-
lined above or remote access program such as EmoSoftCom.
For further information about the control panel, EmoSoft-
Com and menu structure, see the software instruction
5.2.2 Language
Menu [100], “Preferred View” is displayed when started.
Navigate to menu [211] or press toggle button once and you
will jump directly to menu [211].
“[211] Language” – Set preferred language.
5.2.3 Set the Motor Data
Navigate to menu [221] or press toggle button once and you
will jump directly to menu [221].
Enter correct motor data for the connected motor. Change
settings using the keys on the control panel. For further
information about the control panel and menu structure, see
the software instruction.
1. Set motor voltage [221].
2. Set motor frequency [222].
3. Set motor power [223].
4. Set motor current [224].
5. Set motor speed [225].
6. Set power factor (cos
ϕ
) [227].
7. Press toggle button to continue.