CG Drives & Automation 01-5965-01r1
Getting Started
9
4.3
Auto set performed at normal pumping -
pumping water
1. Check that the amount of water is sufficient for pumping about 30 seconds
without snoring.
2. Switch on the supply voltage to the Emotron DCM and set any pump
system control equipment to the on position, “1” or Auto. The pump
should now be pumping water without snoring. If the pump does not start,
press the
button on the Emotron DCM.
3. Step with the
button to window 13 and check that the line is shown at
the top of the display (¯). If not, press
, then press
to confirm.
4. When the pump is working in steady state, press
until “SEt” is shown
on the display. The stop level is now set.
The stop function is now initiated and the Emotron DCM controls the pump.
Adjustments can be made according to Section 6.2, page 30. See also section 6.3
and 6.4.
Fig. 2
Auto set performed at normal pumping
NEXT
ENTER
ENTER
SET
AUTO
SET
AUTO
Power pump motor
Auto set is pressed
Normal pump load power (window 04)
Stop level (window 11)
Power level
when snoring
Time
Snore margin (window 12)
Содержание DCM
Страница 1: ...Emotron DCM Control Unit Instruction manual English...
Страница 2: ......
Страница 6: ...2 Inside the Box CG Drives Automation 01 5965 01r1...
Страница 8: ...4 Safety CG Drives Automation 01 5965 01r1...
Страница 28: ...24 Installation CG Drives Automation 01 5965 01r1...
Страница 36: ...32 Single Pump System Installation CG Drives Automation 01 5965 01r1...
Страница 46: ...42 Protection and Alarm CG Drives Automation 01 5965 01r1...
Страница 54: ...50 Technical Data CG Drives Automation 01 5965 01r1...
Страница 60: ...56 Window Parameters CG Drives Automation 01 5965 01r1...
Страница 62: ...58 Service CG Drives Automation 01 5965 01r1...
Страница 64: ...60 Appendix CG Drives Automation 01 5965 01r1 Fig 19 Dual pump example Figur 16...
Страница 65: ......