EAOM-72F

AutomaticGeneratorStartControllerwithMetering,Flat

T

ype

- Automatic engine start / stop
- Automatic shutdown on fault condition
- LED status and fault indication
- Alternator voltage and frequency measurement and monitoring
- Battery voltage measurement and monitoring
- Simple push-button controlled operation
- Over / under speed warning and shutdown
- Remote start / stop input
- Three user

inputs

- Three Resistive Sender Inputs
- Provides charge alternator excitation current
- Two configurable outputs
- Speed sensing from alternator frequency or magnetic pickup
- Fully programmable
- RS-232 communication port

- Monitors

Three phase alternator voltage

Engine temperature

Three phase current input

Fuel level

Alternator power

Battery voltage

Alternator frequency

Engine running time

Engine speed

Error indication

Oil pressure

Program parameters

- Controls

Engine fuel supply or stopping

Automatic generator start and stop

Starter motor

Preheat

Alarm horn

- Fail Monitoring

Alternator Voltage, Frequency

Engine Start

Engine Speed

Charge Generator Voltage

Engine Temperature

Emergency Stop

Oil Pressure

Maintenance Due

configurable

- Standard modem communication

Instruction Manual. ENG

02 V02 04/21

EAOM-72F

EAOM-72F

Automatic Generator Start Controller

with Metering, Flat Type

SOFT

EAOM-72F

PC Communication Software for

Programming and Remote Monitoring

Содержание EAOM-72F

Страница 1: ...able RS 232 communication port Monitors Three phase alternator voltage Engine temperature Three phase current input Fuel level Alternator power Battery voltage Alternator frequency Engine running time...

Страница 2: ...rs description of the parameters are explained EAOM 72F CONTENTS Installation Operation and Parameters Also in these sections there are warnings to prevent serious injury while doing the physical and...

Страница 3: ...TOR PARAMETERS WINDOW 4 3 8 TECHNICIAN PARAMETERS WINDOW 4 3 9 MAIN MENU 4 3 9 1 FILE 4 3 9 2 PROGRAMMING 4 3 9 3 SETTINGS 4 3 10 ENTERING TO THE OPERATOR PARAMETERS WINDOW 4 3 11 ENTERING TO THE TECH...

Страница 4: ...LTAGE MESSAGE bAT1 9 1 13 WEAK BATTERY ALARM MESSAGE bAT2 9 1 14 HIGH BATTERY VOLTAGE MESSAGE bAT3 9 1 15 ROUTINE MAINTENANCE DUE SErV 9 1 16 OVER CURRENT ocr 5 1 22 OIL PRESSURE SWITCH SENDER SELECTI...

Страница 5: ...Category Electrical equipment for measurement control and laboratory use Conforms to the following directives EAOM 72F Electrical control equipment for generating sets EAOM 72F EMC BS EN 50081 2 EMC...

Страница 6: ...equency Engine RPM Battery voltage Engine running time Load current and power Oil pressure value Coolant system temperature Fuel tank level value Error indication Program parameters The unit is extens...

Страница 7: ...C PICK UP FAILURE CONTROL INPUTS PUSH BUTTONS MAGNETIC PICK UP ANALOG TO DIGITAL CONVERTER COUNTER TIMER MICROCONTROLLER TRANSISTOR OUTPUTS RS 232 MODEM COMM POWER SUPPLY FAILURE STATUS INDICATORS 7 1...

Страница 8: ...are determined in warranty document and instruction manual performs by the customer completely 1 3 Maintenance Repairs should only be performed by trained and specialized personnel Cut power to the d...

Страница 9: ...to use the rated power supply voltage to protect the unit against damage and to prevent failure Keep the power off until all of the wiring is completed so that electric shock and trouble with the uni...

Страница 10: ...2 1 General Description 2 2 Dimensions 10 Mounting Holes Terminal Connection Front Panel IP65 protection NEMA 4X Label Pockets 144mm 204mm Figure 2 1 Front View 10 5 mm 26 5 mm Figure 2 2 Side View...

Страница 11: ...n condensing Up to 2000m C Operating Conditions Forbidden Conditions Corrosive atmosphere Explosive atmosphere Home applications The unit is only for industrial applications 2 4 Environmental Ratings...

Страница 12: ...screws are on the unit put out them before inserting the unit to the panel 2 5 Panel Mounting c 1 3 2 2 2 2 4 The unit is designed for panel mounting Insert the unit in the panel cut out from the fro...

Страница 13: ...1 Loosen the screws 2 Pull the unit through the front side of the panel Before starting to remove the unit from panel power off the unit and the related system 2 7 Removing from the Panel c RESET 13 2...

Страница 14: ...ent to the manufacturer for repair You must ensure that the device is correctly configured for your application Incorrect configuration could result in damage to the process being controlled and or pe...

Страница 15: ...UTPUT SWITCHED POSITIVE OR NEGATIVE SUPPLY TRANSISTOR OUTPUT MAX 500mA BATTERY BATTERY FUSE 1 BATTERY D W L CHARGE GENERATOR Magnetic Pickup up to 10kHz PRESSURE SENDER TEMPERATURE SENDER LEVEL SENDER...

Страница 16: ...bit input 17 Emergency stop input 18 Input from high temperature switch 19 Input from low oil pressure switch 20 Input from charge generator 21 Current measuring input common 22 Current measuring inpu...

Страница 17: ...on panel Configurable failure input 1 Normally open When switched to 0 volt it can be 16 programmed to sound the horn and flash indicator on panel Input from remote start switch Normally open contact...

Страница 18: ...onnector female EAOM 72F Standard communication cable 9 pin D connector male EAOM 72F MODEM communication cable Green Yellow White Brown Brown White Green Note For 9600 baud rate cable length must be...

Страница 19: ...drive on the PC CD will autostart then select EAOM 72F Install exe from the menu Press the windows START button icon then select EAOM 72F SW EAOM 72F from the program menu EAOM 72F EAOM 72F EAOM 72F...

Страница 20: ...nance Hour RunningTime Power Outputs Start Relay Horn Relay Solenoid Relay Configurable Relay Output 1 2 4 3 6 Observation Window 20 Failures Failed to Start Low Oil Pressure HighTemperature Voltage F...

Страница 21: ...u allows the user to print the parameters This menu allows the user to select the printer that is connected to network or PC and change the configuration of the printer Exit the program This menu is a...

Страница 22: ...lish can be selected If this selection is checked after downloading parameters are read to check if they are the same with the downloaded parameters Click Operator Parameter tab Enter the Operator Par...

Страница 23: ...f password is correct all parameters will be viewed 4 3 11 Entering to the Technician Parameters Window Click Technician Parameter tab Enter the Technician Parameter password If password is correct al...

Страница 24: ...Parameters Window all parameters will be loaded Press Download in Program menu While loading the parameters the hour glass cursor is displayed Please wait for the download operation to complete when...

Страница 25: ...999 Second Second 99 1 2 3 Series Delta 50 0 60 0 Hz 500 5000 RPM 1 1000 0 99 Second Battery Voltage Weak Limit 6 0 14 4 VZ 1 Second 99 VV 360 40 20 0 45 0 Hz 1 10 5 99 Second 0 99 Second Control On...

Страница 26: ...ts P39 P39 0 For Configurable Failure Input 1 P39 1 For Configurable Failure Input 2 P39 2 For Configurable Failure Input 3 0 0 0 0 Configurable Output 1 P40 0 16 0 0 Alarm out 1 Engine running 2 Load...

Страница 27: ...current 7 High temperature 16 Weak battery P42 Oil Pressure Switch Sender Selection 0 0 Switch 1 Sender Pressure Lower Limit P43 0 0 99 9 42 6 Pressure Configuration P44 0 2 1 0 Disable the analog inp...

Страница 28: ...en running for the period defined as the Control on Delay P31 This failure immediately stops the generating set without Engine Cooling Time P34 There are four possible system types P11 1 Single phase...

Страница 29: ...pick up Frequency and speed is monitored so as to detect when engine has started and if there is a generator frequency failure See Sections 5 1 2 Alternator Frequency 5 1 13 Engine started signals P18...

Страница 30: ...tor and energises the Fuel solenoid if selected see Section 5 1 11 Stop Fuel Solenoid selection P17 to provide fuel for the engine If the unit detects that the engine has started it de energises the s...

Страница 31: ...Preheat Time P10 The current transformer input output ratio can be entered into parameter Current Transformer Ratio P15 allowing the primary current value to be displayed Example If the CT is 50 5A s...

Страница 32: ...ter Oil Pressure Switch Sender Selection P42 as the source of the oil pressure signal The sender limit Pressure Lower Limit P43 is used as the starting signal and to shut down the engine if the analog...

Страница 33: ...Alternator Voltage Lower Limit P00 to Preheat Time P10 and Operator Password P49 Use this option to change the Technician password It allows access to the all parameters from Alternator Voltage Lower...

Страница 34: ...s Operator Menu Entering screen is shown and prog led lights on PROG RESET TEST PROG RESET TEST When button is pressed operator password entering screen is shown PROG RESET TEST Operator Password Ente...

Страница 35: ...alue Alternator Voltage Lower Limit Value Alternator Voltage Lower Limit Parameter Alternator Voltage Upper Limit Parameter Press button for accessing to the value Press button for saving the value an...

Страница 36: ...on PROG RESET TEST PROG RESET TEST When button is pressed for 10 seconds technician menu entering screen is shown PROG RESET TEST Technician Password Entering Screen Change the password with and butto...

Страница 37: ...lue Alternator Voltage Lower Limit Value Alternator Voltage Lower Limit Parameter Alternator Voltage Upper Limit Parameter Press button for accessing to the Value Press button for saving the value and...

Страница 38: ...eck that the Failed to Start LED flashes Check that the alarm horn sound Press the SilenceAlarm button 5 Restore the engine to operational state reconnect the fuel solenoid Press the Reset button 6 Th...

Страница 39: ...s the unit into Programming mode 6 Up Reset Restores unit operation after it has latched in a fault condition The Increment up arrow function is used in Programming mode as detailed in Section 5 Param...

Страница 40: ...gnetic pick up as selected by Speed Sensing Input Selection P16 Battery Voltage VBAT Engine running time in hours since last reset via Engine Running Time Reset P35 This is a six digit number The firs...

Страница 41: ...LEDs 10 and 9 should both be illuminated after the control on delay period P31 All alarm indicators should remain off 8 3 Starting the Engine When the STOP button is pressed or the Remote Start input...

Страница 42: ...charge generator fails after the engine has started The fault will not be indicated if it occurs within the period defined by the Control On Delay P31 after the engine has started This failure will n...

Страница 43: ...tenance set by program parameter Periodic Maintenance Hour Set Value P07 has expired On completion of the required engine maintenance reset the maintenance timer using Periodic Maintenance Hour Reset...

Страница 44: ...l solenoid and wiring fuel and battery Reset the and restart the engine EAOM 72F Check solenoid transistor output activated Fuel Solenoid if selected Check the signals that the is using to determine i...

Страница 45: ...lue Speed Limit For Crank Disconnection Battery Voltage Weak Control Time Engine Cooling Time 0 disable Periodic Maintenance Hour Reset Horn Duration 0 Continuous Charge Generator Alternator Voltage A...

Страница 46: ...00 Temperature Configuration P46 0 2 Level Lower Limit P47 0 300 Level Configuration P48 0 2 Operator Password P49 0 9990 Technician Password P50 0 9990 Configurable Output 2 P41 0 16 Observing Time o...

Страница 47: ...VL N 1 of range Voltage and Current 2 of range Resistive Battery voltage can be 0V for max 100msn during cranking battery voltage should be at least nominal voltage before cranking From alternator or...