NetSure
™
-48 VDC Power System
Installation Instructions, IM582127000100 (Revision A, January 9, 2017)
Spec. No: 582127000100, 582127000103
Document Code: IM582127000100
Model No: 7100
Revision A, January 9, 2017
[28]
Table 6.
Programmable Digital Inputs – IB2 Board
Programmable
Digital Input
IB2
Pin No.
Factory
Wiring
Default Digital
Input Function
Customer Defined
Digital Input Function
1
J3-2
+
The digital inputs may be
preprogrammed for specific
functions and have factory
wiring connected. Refer to
the configuration drawing
(C-drawing) supplied with
your system for your
system’s specific
configuration.
The digital inputs may be
preprogrammed for specific
functions. Refer to the
configuration drawing (C-
drawing) supplied with your
system for your system’s
specific configuration.
J3-1
–
2
J3-4
+
J3-3
–
3
J3-6
+
J3-5
–
4
J4-2
+
J4-1
–
5
J4-4
+
J4-3
–
6
J4-6
+
J4-5
–
7
J5-2
+
J5-1
–
8
J5-4
+
(to customer
ESTOP switch)
ESTOP
J5-3
–
-48 VDC
--
J5-5
not used
not used
not used
--
J5-6
NOTE: -48V is factory wired to the Digital Input #8 (-) terminal for your convenience and function predefined for ESTOP.
Customer-furnished system ground applied to terminal Digital Input #8 (+) activates the ESTOP function. The ESTOP function
shuts down and locks out the rectifiers, opens the battery disconnect contactor, and shuts down the -48 VDC to +24 VDC
converters. When the ESTOP signal is removed, the battery disconnect contactor closes (if battery present) and -48 VDC to +24
VDC converters restart. To restart the rectifiers; turn input power to the rectifiers OFF, wait 30 seconds or more (until the LEDs
on the rectifiers extinguish), then turn input power to the rectifiers ON.