Emerson Wireless Field Link Скачать руководство пользователя страница 1

Quick Start Guide

00825-0100-4421, Rev DB

February 2019

Emerson

 Wireless Field Link

Содержание Wireless Field Link

Страница 1: ...Quick Start Guide 00825 0100 4421 Rev DB February 2019 Emerson Wireless Field Link ...

Страница 2: ...tandards codes and practices Review the Product Certifications section for any restrictions associated with a safe installation Electrical shock can result in death or serious injury Avoid contact with the leads and terminals High voltage may be present on leads can cause electrical shock This device complies with Part 15 of the FCC Rules Operation is subject to the following conditions This devic...

Страница 3: ...s will result in a simpler and faster network installation 1 2 Mounting location The Field Link should be mounted in a location that allows convenient access to the host system network wireless I O as well as the wireless field device network Find a location where the Field Link has optimal wireless performance Ideally this will be 15 to 25 ft 4 6 to 7 6 m above the ground or 6 ft 2 m above obstru...

Страница 4: ... and should be approximately 3 ft 1 m from any large structure building or conductive surface to allow for clear communication to other devices Figure 2 Antenna Position 1 4 Conduit plug The temporary orange plugs should be replaced with the included conduit plugs using approved thread sealant Figure 3 Conduit Plugs A Conduit plug A A ...

Страница 5: ... 2 1 Pipe mounting 1 Insert larger U bolt around 2 in pipe mast through the saddle through the L shaped bracket and through the washer plate 2 Use a 1 2 in socket head wrench to fasten the nuts to the U bolt 3 Insert smaller U bolt around base the Field Link and through the L shaped bracket 4 Use a 1 2 in socket head wrench to fasten the nuts to the U bolt Figure 5 Mounting A Host system B Control...

Страница 6: ...ways be grounded in accordance with national and local electrical codes The most effective grounding method is a direct connection to earth ground with minimal impedance Ground the Field Link by connecting the external ground lug to earth ground The connection should be 1 or less 3 0 Verify operation 3 1 Power up sequence Upon applying power to the Field link the LCD display meter will activate an...

Страница 7: ...ce Usage The Field Link will continue to rotate through each periodic screen through the course of normal operation If any diagnostic or fault condition occurs a corresponding diagnostics screen will appear 4 0 Reference information Figure 7 Emerson Wireless Field Link Terminal Diagram Note The Emerson Wireless Field Link requires separate twisted shield pairs four wires for power and data A Data ...

Страница 8: ... AWG twisted shielded pair 1 1 Ambient temperatures above 60 C require wiring rated to at least 5 C above max ambient temperature Wiring RS 485 communications 24 AWG 14 AWG twisted shielded pair1 Less than 15 pF ft capacitance Wiring distance 656 ft 200 m Wireless protocol WirelessHART 2 4 2 5 GHz DSSS Wireless output power EIRP 10 dBm with WK antenna and 12 5 dBm with WM antenna Mounting All SST ...

Страница 9: ...l Conduit threads 1 1 2 14 NPT 2 M20 Product certifications I5 USA Intrinsically Safe Non incendive I6 Canada Intrinsically Safe I1 ATEX Intrinsic Safety I7 IECEx Intrinsic Safety KD USA and Canada Intrinsically Safe ATEX and IECEx Intrinsic Safety I2 INMETRO Intrinsic Safety I4 Japan Intrinsic Safety IM EAC Intrinsic Safety I3 China NEPSI Intrinsic Safety KL USA and Canada Intrinsic Safety ATEX I...

Страница 10: ...0 Quick Start Guide Options Include with selected model number Meter M5 LCD display Gland and connector options G2 Cable gland 7 5 11 9 mm G4 Thin wire cable gland 3 8 mm Typical model number 781 A1 D 1 KL WA3 WK3 M5 ...

Страница 11: ...X Standards FM Class 3600 2011 FM Class 3610 2010 FM Class 3611 2004 FM Class 3810 2005 ANSI ISA 60079 0 2009 ANSI UL 60079 11 2009 ANSI ISA 61010 1 2004 ANSI NEMA 250 2003 ANSI IEC 60529 2004 Markings IS CL I DIV 1 GP A B C D CL II DIV 1 GP E F G Class III T4 Class 1 Zone 0 AEx ia IIC T4 NI CL I DIV 2 GP A B C D T4 DIP CL II DIV 1 GP E F G CL III T4 when installed per drawing 00781 1010 T4 40 C T...

Страница 12: ... made of aluminum alloy and given a protective paint finish however care should be taken to protect it from impact or abrasion if located in a zone 0 environment 3 The apparatus is not capable of withstanding the 500 V isolation test required by EN 60079 11 This must be taken into account when installing the apparatus International I7 IECEx Intrinsic Safety Certificate IECEx BAS 11 0028X Standards...

Страница 13: ...40 70 C Special Condition for Safe Use X 1 See certificate for special conditions EAC Belarus Kazakhstan Russia IM EAC Intrinsic Safety Certificate RU C US Gb05 B 00643 Markings 0Ex ia IIC T4 Ga X Special Condition for Safe Use X 1 See certificate for special conditions Japan I4 CML Intrinsic Safety Certificate CML 18JPN2024X Markings Ex ia IIC T4 Ga 40 70 C Special Condition for Safe Use X 1 See ...

Страница 14: ...February 2019 14 Quick Start Guide Combinations KD Combination of I1 I5 and I6 KL Combination of I1 I5 I6 and I7 ...

Страница 15: ...osemount Inc 8200 Market Boulevard Chanhassen MN 55317 9685 USA to which this declaration relates is in conformity with the provisions of the European Union Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of the harmonized standards and when applicable or required a European Union notified body certification as shown...

Страница 16: ...Directive 2014 34 EU Baseefa11ATEX0059X Intrinsic Safety Certificate Equipment Group II Category 1 G Ex ia IIC T4 Ga Standards Used EN 60079 0 2009 A review against EN60079 0 2012 A11 2013 which is harmonized shows no significant changes relevant to this equipment so EN60079 0 2009 continues to represent State of the Art EN 60079 11 2007 A review against EN60079 11 2012 which is harmonized shows n...

Страница 17: ... RMD 1083 Rev H Page 3 of 3 ATEX Notified Body SGS FIMKO OY Notified Body Number 0598 P O Box 30 Särkiniementie 3 00211 HELSINKI Finland ATEX Notified Body for Quality Assurance SGS FIMKO OY Notified Body Number 0598 P O Box 30 Särkiniementie 3 00211 HELSINKI Finland ...

Страница 18: ...ctronics Assembly X O O O O O ༣փ㓴Ԧ Housing Assembly X O O X O O ᵜ㺘Ṭ ᦞ SJ T11364Ⲵ㿴ᇊ㘼ࡦ This table is proposed in accordance with the provision of SJ T11364 O Ѫ䈕䜘ԦⲴᡰᴹ 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿 վҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 O Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 X Ѫ 䈕䜘Ԧᡰ Ⲵᡰᴹ 䍘ᶀᯉ䟼ˈ㠣ቁᴹа 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿儈ҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 X Indicate t...

Страница 19: ...Quick Start Guide 19 February 2019 ...

Страница 20: ...t Emerson Terms and Conditions of Sale are available upon request The Emerson logo is a trademark and service mark of Emerson Electric Co Rosemount is a mark of one of the Emerson family of companies All other marks are the property of their respective owners 2019 Emerson All rights reserved Europe Regional Office Emerson Automation Solutions Neuhofstrasse 19a P O Box 1046 CH 6340 Baar Switzerland...