Table 12-2 Maximum permissible continuous output current @ 40 °C (104 °F) ambient with high IP insert installed
Model
Normal Duty
Heavy Duty
Maximum permissible continuous output current (A)
for the following switching frequencies
Maximum permissible continuous output current (A)
for the following switching frequencies
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
200 V
03200050
6.6
5.0
03200066
8.0
6.6
03200080
11.0
9.7
8.0
6.9
03200106
12.7
11.0
9.7
10.6
10.4
9.3
8.0
6.9
04200137
18.0
16.3
14.2
13.1
13.7
13.2
04200185
24.7
22.5
20.7
18.2
16.5
14.2
13.2
18.5
18.1
16.2
14.2
13.1
05200250
17.1
15.6
14.4
12.6
11.4
9.6
8.7
17.0
15.7
14.5
12.7
11.5
9.8
9.8
400 V
03400025
3.4
3.3
2.5
03400031
4.5
4.4
4.1
3.6
3.3
3.1
03400045
5.1
4.9
4.7
4.4
4.1
3.6
3.3
4.5
4.4
4.1
3.6
3.2
03400062
7.7
6.2
5.2
6.2
5.6
4.5
3.8
03400078
10.4
9.9
9.0
6.4
4.8
7.8
6.6
4.8
3.6
03400100
12.3
11.9
11.1
10.0
9.0
6.4
4.8
10.0
9.4
7.8
6.6
4.8
3.6
04400150
8.9
8.7
8.3
7.0
8.7
8.4
7.0
04400172
8.6
8.4
6.9
8.7
8.4
7.0
05400270
17.1
15.6
14.4
12.6
11.4
9.6
8.7
17.2
15.6
14.5
12.6
11.3
9.7
8.6
05400300
19.8
19.5
18.9
17.6
16.4
13.9
11.7
19.8
19.5
18.9
17.7
16.2
13.8
11.7
575 V
05500030
3.9
3.0
05500040
6.1
4.0
05500069
10.0
6.9