Unidrive M400 User Guide
63
Issue Number: 2
5.3.1 CI-Keypad set-up menu
To enter the keypad set-up menu, press and hold the Escape
button on the keypad from status mode. All the keypad parameters are
saved to the keypad non-volatile memory when exiting from the keypad
set-up menu. To exit from the keypad set-up menu, press the
Escape
or
or
button. Below are the keypad set-up
parameters.
Table 5-4 CI-Keypad set-up parameters
It is not possible to access the keypad parameters via any
communications channel.
5.4 Advanced menus
The advanced menus consist of groups or parameters appropriate to a
specific function or feature of the drive. Menus 0 to 24 can be viewed on
the Keypad.
The option module menu (S.mm.ppp) is only displayed if the option
module is installed. Where S signifies the option module slot number
and the mm.ppp signifies the menu and parameter number of the option
module’s internal menus and parameter.
Table 5-5 Advanced menu descriptions
* Only displayed when the option module is installed.
5.4.1 Display messages
The following tables indicate the various possible mnemonics which can
be displayed by the drive and their meaning.
Table 5-6 Status indications
5.4.2 Alarm indications
An alarm is an indication given on the display by alternating the alarm
string with the drive status string on the display. Alarms strings are not
displayed when a parameter is being edited.
Table 5-7 Alarm indications
Parameters
Range
Type
Keypad.00 Language
Classic English
or English
RW
Keypad.01 Show Units
Off or On
RW
Keypad.02 Backlight Level
0 to 100 %
RW
Keypad.05 Show Raw Text Parameter Values Off or On
RW
Keypad.06 Software Version
00.00.00.00 to
99.99.99.99
RO
Menu
Description
0
Commonly used basic set up parameters for quick / easy
programming
1
Frequency reference
2
Ramps
3
Frequency control
4
Torque and current control
5
Motor control
6
Sequencer and clock
7
Analog I/O
8
Digital I/O
9
Programmable logic, motorized pot, binary sum, timers
10
Status and trips
11
Drive set-up and identification, serial communications
12
Threshold detectors and variable selectors
14
User PID controller
15
Option module slot 1 set-up menu
18
General option module application menu 1
20
General option module application menu 2
21
Second motor parameters
22
Menu 0 set-up
Slot 1
Slot 1 option menus*
NOTE
Upper row
string
Description
Drive
output
stage
Inhibit
The drive is inhibited and cannot be run.
The SAFE TORQUE OFF signals are not
applied to the SAFE TORQUE OFF
terminals or Pr
06.015
is set to 0. The other
conditions that can prevent the drive from
enabling are shown as bits in Enable
Conditions (06.010).
Disabled
Ready
The drive is ready to run. The drive enable
is active, but the drive inverter is not active
because the final drive run is not active.
Disabled
Stop
The drive is stopped / holding zero
frequency.
Enabled
Run
The drive is active and running.
Enabled
Supply Loss
Supply loss condition has been detected
Enabled
Deceleration
The motor is being decelerated to zero
frequency because the final drive run has
been deactivated.
Enabled
dc Injection
The drive is applying dc injection braking.
Enabled
Trip
The drive has tripped and no longer
controlling the motor. The trip code
appears in the lower display.
Disabled
Under
Voltage
The drive is in the under voltage state
either in low voltage or high voltage mode.
Disabled
Alarm string
Description
Brake Resistor
Brake resistor overload.
Braking Resistor Thermal
Accumulator
(10.039) in the drive has reached 75.0
% of the value at which the drive will trip.
Motor Overload
Motor Protection Accumulator
(04.019) in the drive
has reached 75.0 % of the value at which the drive
will trip and the load on the drive is >100 %.
Drive overload
Drive over temperature.
Percentage Of Drive
Thermal Trip Level
(07.036) in the drive is greater
than 90 %.
Auto Tune
The autotune procedure has been initialized and an
autotune in progress.
Limit Switch
Limit switch active. Indicates that a limit switch is
active and that is causing the motor to be stopped.
Option Slot 1
Option slot alarm.
Low AC
Low voltage mode. See Low AC Alarm (10.107).
Current Limit
Current limit active. See Current Limit Active
(10.009).