Unidrive M400 User Guide
141
Issue Number: 2
11.11 Menu 11: General drive set-up
Parameter
Range (
Ú
)
Default (
Ö
)
Type
OL
RFC-A
OL
RFC-A
11.018
Status Mode Parameter 1
0.000 to 30.999
2.001
RW Num
PT US
11.019
Status Mode Parameter 2
0.000 to 30.999
4.020
RW Num
PT US
11.020
Reset Serial Communications
Off (0) or On (1)
RW
Bit
ND NC
11.021
Customer defined scaling
0.000 to 10.000
1.000
RW Num
US
11.022
Parameter Displayed At Power-up
0.000 to 0.080
0.010
RW Num
PT US
11.023
Serial Address
1 to 247
1
RW Num
US
11.024
Serial Mode
8 2 NP (0), 8 1 NP (1), 8 1 EP (2),
8 1 OP (3), 8 2 NP M (4), 8 1 NP M (5),
8 1 EP M (6), 8 1 OP M (7), 7 1 EP (8),
7 1 OP (9), 7 1 EP M (10),
7 1 OP M (11)
8 2 NP (0)
RW
Txt
US
11.025
Serial Baud Rate
300 (0), 600 (1), 1200 (2), 2400 (3),
4800 (4), 9600 (5), 19200 (6),
38400 (7), 57600 (8), 76800 (9),
115200 (10)
19200 (6)
RW
Txt
US
11.026
Minimum Comms Transmit Delay
0 to 250 ms
2 ms
RW Num
US
11.027
Silent Period
0 to 250 ms
0 ms
RW Num
US
11.028
Drive Derivative
0 to 255
RO
Num ND NC PT
11.029
Software Version
00.00.00.00 to 99.99.99.99
RO
Ver
ND NC PT
11.030
User Security Code
0 to 9999
RW Num ND NC PT US
11.031
User Drive Mode
Open-loop (1), RFC-A (2)
RW
Txt
ND NC PT
11.032
Maximum Heavy Duty Rating
0.00 to 9999.99 A
RO
Num ND NC PT
11.033
Drive Rated Voltage
110V (0), 200V (1), 400V (2),
575V (3), 690V (4)
RO
Txt
ND NC PT
11.034
Drive Configuration
AV (0), AI (1), AV Preset (2),
AI Preset (3), Preset (4), Keypad (5),
Keypad Ref (6), Electronic Pot (7),
Torque Control (8), Pid Control (9)
AV (0)
RW
Txt
PT US
11.035
Power Software Version
00.00.00.00 to 99.99.99.99
RO
Ver
ND NC PT
11.036
NV Media Card File Previously
Loaded
0 to 999
0
RO
Num
NC PT
11.037
NV Media Card File Number
0 to 999
0
RW Num
11.038
NV Media Card File Type
None (0), Open-loop (1), RFC-A (2),
User Program (5)
RO
Txt
ND NC PT
11.039
NV Media Card File Version
0 to 9999
RO
Num ND NC PT
11.042
Parameter Cloning
None (0), Read (1), Program (2),
Auto (3), Boot (4)
None (0)
RW
Txt
NC
US
11.043
Load Defaults
None (0), Standard (1), US (2)
None (0)
RW
Txt
NC
11.044
User Security Status
Menu 0 (0), All Menus (1),
Read-only Menu 0 (2), Read-only (3),
Status Only (4), No Access (5)
RW
Txt
ND
PT
11.045
Select Motor 2 Parameters
Motor 1 (0), Motor 2 (1)
Motor 1 (0)
RW
Txt
US
11.046
Defaults Previously Loaded
0 to 2000
RO
Num ND NC PT US
11.047
Onboard User Program: Enable
Stop (0), Run (1)
Run (1)
RW
Txt
US
11.048
Onboard User Program: Status
-2147483648 to 2147483647
RO
Num ND NC PT
11.049
Onboard User Program:
Programming Events
0 to 65535
RO
Num ND NC PT
11.050
Onboard User Program:
Freewheeling Tasks Per Second
0 to 65535
RO
Num ND NC PT
11.051
Onboard User Program: Clock Task
Time Used
0.0 to 100.0 %
RO
Num ND NC PT
11.052
Serial Number LS
000000 to 999999
RO
Num ND NC PT
11.053
Serial Number MS
0 to 999999
RO
Num ND NC PT
11.054
Drive Date Code
0000 to 9999
RO
Num ND NC PT
11.055
Onboard User Program: Clock Task
Schedule Rate
0 to 262128
RO
Num ND NC PT
11.060
Maximum Rated Current
0.000 to 999.999
RO
Num ND NC PT
Содержание Unidrive M400