9.2 Menu 0: Basic parameters
Table 9-2 Unidrive SP Regen menu 0 parameter descriptions
* Modes 1 and 2 are not user saved, Modes 0, 3 and 4 are user saved
Parameter
Range(
Ú
)
Default(
Ö
)
Type
0.00
xx.00
0 to 32,767
0
RW Uni
0.01
Voltage setpoint
{
3.05
}
0 to DC_VOLTAGE_SET_MAX V
700 Vdc
RW Uni
US
0.02
Voltage controller Kp gain
{
3.06
}
0 to 65535
4000
RW Bi
US
0.03
Enable motor drive
{
3.09
}
OFF (0) or On (1)
RO Uni
NC
0.04
DC bus voltage
{
5.05
}
0 to +DC_VOLTAGE_MAX V
RO Uni FI NC PT
0.05
Output / supply voltage
{
5.02
}
0 to AC_VOLTAGE_MAX V
RO Uni FI NC PT
0.06
Regen drive status
{
3.03
}
0 to 15
RO Uni
NC PT
0.07
Regen restart mode
{
3.04
}
0 to 2
1
RW Uni
US
0.08
Close soft start contactor
{
3.07
}
OFF (0) or On (1)
RO Uni
NC
0.09
Soft start contactor closed
{
3.08
}
OFF (0) or On (1)
RO Uni
NC
0.10
Power feed forward compensation
{
3.10
}
±100.0 %
0.0
RW Bi
NC
0.11
Output / supply frequency
{
5.01
}
±100.0 Hz
RO Bi
FI NC PT
0.12
Current magnitude
{
4.01
}
0 to DRIVE_CURRENT_MAX A
RO Uni FI NC PT
0.13
Active current
{
4.02
}
±DRIVE_CURRENT_MAX A
RO Bi
FI NC PT
0.14
Output / supply power
{
5.03
}
±POWER_MAX kW
RO Bi
FI NC PT
0.15
Reactive power
{
3.01
}
±POWER_MAX kVAR’s
RO Bi
FI NC PT
0.16
Input inductance
{
3.02
}
0.000 to 500.000 mH
RO Uni
NC PT
0.17
Reactive current reference
{
4.08
}
±REGEN_REACTIVE_MAX %
0.0
RW Bi
US
0.18
Positive logic select
{
8.29
}
OFF (0) or On (1)
On (1)
RW Bit
PT US
0.19
T7 analogue input 2 mode
{
7.11
}
0-20 (0), 20-0 (1), 4-20.tr (2), 20-4.tr (3),
4-20 (4), 20-4 (5), VOLt (6)
VOLt (6)
RW Txt
US
0.20
T7 analogue input 2 destination
{
7.14
}
Pr
0.00
to
21.51
Pr
3.10
RW Uni DE
PT US
0.21
T8 analogue input 3 mode
{
7.15
}
0-20 (0), 20-0 (1), 4-20.tr (2), 20-4.tr (3),
4-20 (4), 20-4 (5), VOLt (6), th.SC (7),
th (8), th.diSP (9)
VOLt (6)
RW Txt
US
0.22
Not used
0.23
Not used
0.24
Not used
0.25
Not used
0.26
Not used
0.27
Not used
0.28
Not used
0.29
SMARTCARD parameter data
previously loaded
{
11.36
}
0 to 999
0
RO Uni
NC PT US
0.30
Parameter cloning
{
11.42
}
nonE (0), rEAd (1), Prog (2), AutO (3),
boot (4)
nonE (0)
RW Txt
NC
*
0.31
Drive voltage rating
{
11.33
}
200 (0), 400 (1), 575 (2), 690 (3)
RO Txt
NC PT
0.32
Maximum Heavy Duty current rating
{
11.32
}
0.00 to 9999.99A
RO Uni
NC PT
0.33
Not used
0.34
User security code
{
11.30
}
0 to 999
0
RW Uni
NC PT PS
0.35
Serial mode
{
11.24
}
AnSI (0), rtU (1)
rtU (1)
RW Txt
US
0.36
Baud rate
{
11.25
}
300 (0), 600 (1), 1200 (2), 2400 (3), 4800 (4),
9600 (5), 19200 (6), 38400 (7),
57600 (8)*, 115200 (9)* *Modbus RTU only
19200 (6)
RW Txt
US
0.37
Serial address
{
11.23
}
0 to 247
1
RW Uni
US
0.38
Current controller Kp gain
{
4.13
}
0 to 30,000
45
RW Uni
US
0.39
Current controller Ki gain
{
4.14
}
0 to 30,000
1,000
RW Uni
US
0.40
Not used
0.41
Maximum switching frequency
{
5.18
}
0 to 5 (3, 4, 6, 8, 12, 16 kHz)
0 (3kHz)
RW Uni
US
0.42
Not used
0.43
Not used
0.44
Not used
0.45
Thermal time constant
{
4.15
}
0.0 to 400.0
89.0
RW Uni
US
0.46
Regen drive rated current
{
5.07
}
0 to RATED_CURRENT_MAX A
RW Uni
US
0.47
Not used
0.48
User drive mode
{
11.31
}
OPEn LP (1), CL VECt (2),
SErVO (3), rEGEn (4)
rEGEn (4)
RW Txt
NC PT
0.49
Security status
{
11.44
}
L1 (0), L2 (1), Loc (2)
L2 (1)
RW Txt
PT US
0.50
Software version
{
11.29
}
1.00 to 99.99
RO Uni
NC PT
0.51 to
0.59
Not used
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not cloned
RA
Rating dependent
PT
Protected
US
User save
PS
Power down save