Unidrive SP Regen Installation Guide
www.controltechniques.com Issue Number: 2
The powered-up clock always starts at zero each time the drive is powered-up. The time can be changed by the user from the keypad, serial comms
or an application module. If the data is not written with the various parts in the correct range (i.e. minutes are greater than 59, etc.) the clock is set to
zero on the next minute. This clock may be used for time stamping the trip log if Pr
6.28
= 0.
The run time clock increments when the drive inverter is active to indicate the number of minutes that the drive has been running since leaving the
Control Techniques factory. This clock may be used for time stamping the trip log if Pr
6.28
= 1.
Pr
6.24
and Pr
6.25
form the energy meter that indicates energy supplied to/from the drive in kWh. For motor control modes a positive value indicates
net transfer of energy from the drive to the motor. For regen mode a positive value indicates a net transfer of energy from the supply to the drive. The
energy meter is reset and held at zero when Pr
6.17
is one.
Instantaneous read out of the cost/hour of running the drive. This requires Pr
6.16
to be set up correctly.
6.21
Powered-up time: hours.minutes
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU
PS
2
1
1
1
1
1
Range
Regen
0 to 23.59 Hours.Minutes
Update rate
Background
6.22
Run time: years.days
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU
PS
3
1
1
1
1
1
Range
Regen
0 to 9.364 Years.Days
Update rate
Background
6.23
Run time: hours.minutes
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU
PS
2
1
1
1
1
1
Range
Regen
0 to 23.59 Hours.Minutes
Update rate
Background
6.24
Energy meter: MWh
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU
PS
1
1
1
1
1
Range
Regen
±999.9 MWh
Update rate
Background
6.25
Energy meter: kWh
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV
PT
US RW BU
PS
2
1
1
1
1
Range
Regen
±99.99 kWh
Update rate
Background
6.26
Running cost
Drive mode
Regen
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU
PS
1
1
1
1
Range
Regen
±32,000
Update rate
Background