30
SM-I/O 24V Protected User Guide
www.controltechniques.com
Issue Number: 2
*Parameter not available with Commander SK (Analogue output 2 is a load output
only [Pr 4.02]).
The parameter required to be represented as an analogue signal by the analogue
output on terminal 12, should be programmed into this parameter.
The parameter required to be represented as an analogue signal by the analogue
output on terminal 10, should be programmed into this parameter.
This parameter can be used to scale the analogue output if so desired.
The error status is provided so that only one option error trip is required for each
Solutions Module slot. If an error occurs, the reason for the error is written to this
parameter and the drive may produce a ‘SLx.Er’ trip, where x is the slot number (SL.Er
on Commander SK). A value of zero indicates that the Solutions Module has not
detected an error, a non-zero value indicates that an error has been detected. (See
Chapter 6
for the meaning of the values in this parameter.) When the drive
is reset, this parameter is cleared for the relevant Solutions Module.
This Solutions Module includes a temperature monitoring circuit. If the PCB temperature
exceeds 90
°
C, the drive fan is forced to operate at full speed (for a minimum of 10s). If
the temperature falls below 90
°
C, the fan can operate normally again. If the PCB
temperature exceeds 100
°
C, the drive is tripped and the error status is set to 74.
x.47*
Analogue output 2 source
RW
Uni
US
Ú
Pr
0.00
to Pr
21.51
Ö
Pr
0.00
Update rate: Read on reset
x.48
Analogue output 1 source
RW
Uni
US
Ú
Pr
0.00
to Pr
21.51
Ö
Pr
0.00
Update rate: Read on reset
x.49
Analogue output 1 scaling
RW
Uni
US
Ú
0.000 to 4.000
Ö
1.000
Update rate: Background read
x.50
Solutions Module error status
RO
Uni
NC
PT
Ú
0 to 255
Ö
Update rate: Background read
If the PCB temperature exceeds 90
°
C on the Commander SK, the fan will operate at full
speed for a minimum of 20s.
NOTE