XR75CX 2.6
Software Overview
•
5
-
31
5.14 XR75CX 2.6
Model XR75CX 2.6 (32 mm x 74 mm) is a micropro-
cessor based controller, suitable for applications on
medium or low temperature ventilated refrigeration units.
It has four relay outputs to control compressor, fan, and
defrost, which can be either electrical or reverse cycle (hot
gas) and light (configurable). It can have a Real Time
Clock (RTC) that allows programming of up to six daily
defrost cycles, divided into holidays and workdays. A
“Day and Night” function with two different setpoints is
fitted for energy saving.
It can also have up to four NTC or PT1000 probe
inputs; the first one for temperature control and the second
probe is located on the evaporator to control the defrost
termination temperature and to manage the fan. One of the
two digital inputs can operate as a third temperature probe.
The fourth probe is used to signal the condenser
temperature alarm or to display a temperature value.
The RS485 serial output enables the unit to be
connected to a network line that is MODBUS-RTU
compatible, such as the monitoring units of the XWEB
family. The Hot Key receptacle allows the controller to be
programmed by means of the Hot Key programming
keyboard.
The controller is fully configurable through special
parameters that can be easily programmed through the
keyboard.
How To Add an XR75CX 2.6 Device on the Site
Supervisor:
1. From Home screen, navigate to Main Menu>
Summaries and Floor Plans> Site Summaries>
Refrigeration, click the screen drop-down arrow
on the upper right of the screen, click
Add
Controls
.
2. Select the Control or Application Type -
XR75CX 2.6
, enter the Quantity, Control Name
and Serial Type. Note that Serial Type
information can be enter later. Click
Save
to add
the application.
3. A Confirmation box will appear saying that the
application is successfully added to the system,
click
Close
or
Edit these controls
.
4. The system will display the new application(s) on
the Site Summary screen.
5. Click the XR75CX 2.6 application panel box to
view the application.
6. The system will display the XR75CX 2.6
application parameters.
7. The user can view and configure the properties of
the application by setting the Edit Mode to “
ON
”
on the screen drop-down arrow on the upper right
of the screen.
5.14.1 Application Advisories
Figure 5-9
- XR75CX 2.6 Device
Figure 5-10
- XR75CX 2.6 Wiring Connection
Alarm Description
EXTERNAL
ALARM
External alarm
DOOR OPEN
Open Door alarm
EEPROM FAIL-
URE
EEPROM Failure alarm
CASE TEMP FAIL Case temperature probe failure alarm
DEFR TERM FAIL Defrost termination probe failure alarm
HIGH CASE ALM High case temperature alarm
LO CASE ALM
Low case temperature alarm
RTC DATA LOST RTC data lost alarm
RTC FAILURE
RTC failure alarm
Table 5-12
- XR75CX 2.6 Application Advisories
Содержание Site Supervisor
Страница 1: ...026 1800 Rev 3 02 AUG 2016 Site Supervisor Controller User Guide 2 0 ...
Страница 2: ......
Страница 13: ...Wiring Diagrams Hardware Overview 1 3 Figure 1 3 Site Supervisor 2 0 Detail ...
Страница 29: ...Wiring Examples 3 1 3 Wiring Examples Figure 3 1 Site Supervisor and MultiFlex Wiring ...
Страница 31: ...Wiring Examples 3 3 Figure 3 3 Site Supervisor and XR35CX 230V Wiring ...
Страница 33: ...Wiring Examples 3 5 Figure 3 5 Site Supervisor and XR75CX Wiring ...
Страница 35: ...Wiring Examples 3 7 Figure 3 7 Site Supervisor and XM678 Wiring ...
Страница 37: ...Wiring Examples 3 9 Figure 3 9 Site Supervisor and XEV22 Wiring ...
Страница 39: ...Wiring Examples 3 11 Figure 3 11 Site Supervisor and XEV32 Wiring ...
Страница 41: ...Wiring Examples 3 13 Figure 3 13 Site Supervisor and Thermostat Wiring ...
Страница 43: ...Wiring Examples 3 15 Figure 3 14 Site Supervisor and iPro S Wiring ...
Страница 121: ......
Страница 129: ......
Страница 135: ......
Страница 139: ......
Страница 140: ......