SI-PROFINET RT User Guide
33
Issue Number: 2
Saf
ety
In
M
El
G
A
Pa
ra
D
G
A changed value of the revision counter parameter of PROFINET marks a change of
hardware or its parameters. At production, the counter will be set to zero. This value is
reserved for the first installation and the first increment. The counter increments from 1
to 65535, wrapping over back to 1 when required.
Criteria to increment the revision counter
•
If any other than the SI-PROFINET RT module is removed or inserted then
configuration counter will increment since that is a configuration change.
•
Any write access of parameters within the module and its activation.
•
If any user save in the drive or in the module.
The counter will reset to zero when the module is defaulted.
This parameter displays the supported PROFIdrive profile ID. This is fixed at 62976
(0xF600).
This parameter indicates that the date of installation or commissioning of a device or
module. This date will be written by controller and cannot be modified by the user via the
keypad or comms.
S.05.006
Module Revision Counter
Minimum
0
Maximum
65535
Default
0
Units
Type
16 Bit Volatile
Update Rate
On Module Reset
Display Format
None
Decimal Places
0
Coding
RO, ND, PT, BU
S.05.007
Profile ID
Minimum
0
Maximum
65535
Default
62976
Units
Type
16 Bit volatile
Update Rate
Background read
Display Format
None
Decimal Places
0
Coding
RO, PT, BU
S.05.008
Installation Date
Minimum
00-00-00
Maximum
31-12-99
Default
Units
Type
32 Bit volatile
Update Rate
Module reset /
initialization
Display Format
Date
Decimal Places
0
Coding
RO, ND, PT, BU