11.4.11 DriveEnable
Enables the drive. This puts the Drive into the “Ready” state, allowing the RunFwd and
RunRev attributes to control the drive. RunFwd and RunRev will have no effect if
DriveEnable is not set to 1.
Get/Set Pr
06.042
bit 0
11.5
AC/DC Drive Object
Class:
0x2A (42)
11.5.1 AtReference
Indicates that the drive is running at the requested speed.
Get
Pr
10.006
11.5.2 NetRef
Selects the source of the speed reference. Analog input 1 is used as the speed
reference when running under local control, with Digital Speed Reference 1 being used
as the speed reference for network control.
Get/Set Pr
06.042
bit 8
Set False analog speed reference
Set True digital speed reference
The reference can only be changed between local and remote when the drive is
configured in speed control mode. If a change is requested when in torque mode then a
‘Device state conflict’ error code 10h will be returned.
Name:
DriveEnable
Class
0x29
Default
Instance
0x01
Data Type
USINT
Attribute
0x0F
Access
Get/Set
The external hardware enable signal must also be present before the drive will go to the
Ready state.
NOTE
Name:
AtReference
Class
0x2A
Default
Instance
0x01
Data Type
USINT
Attribute
0x03
Access
Get
Name:
NetRef
Class
0x2A
Default
Instance
0x01
Data Type
USINT
Attribute
0x04
Access
Get/Set