Emerson Process Management GmbH & Co. OHG
6-79
X-STREAM XE
Instruction Manual
HASXEE-IM-HS
10/2012
6
Software Menus
6.2.3 Setup Menu
6.2.3.5.2
Setup Communication Ethernetn
Setup..
Communication..
Ethernet
1
…
2
Ethernet1
MAC
123456789
IP:
123.456.78.9
Subnet:
255.255.255.1
Gateway:
123.456.78.0
Use DHCP:
Yes
IP Status
Ready
Apply Configuration!
Ethernet1 Modbus
32Bit Mode:
16BitLow
Modb Timeout:
1000 ms
Modbus mode of operation.
Available options:
32Bit
(=Daniel mode),
16BitLow
(=Modicon mode, LOW word first)
16BitHigh
(=Modicon mode, HIGH word first)
Modbus timeout.
Accepted values:
500 ... 10,000
ms
Note!
At maximum 2 hosts at a time can connect
to the analyzer. "
MBus timeout
" specifies the
time interval to elapse, before a host without
activity is disconnected.
If your network does not feature a DHCP
server, enter these lines to configure the
network settings manually.
If your network does not feature a DHCP
server, select
No
to enter the network set-
tings manually.
If your network features a DHCP server, "
IP
status
" turns to
Ready
, if a valid IP address
has been assigned.
To apply any changes made on this first
menu page, press enter in this line.
Within these menus, configure the Ethernet
communication for connector 1 or 2.
Most entries are standard, to be setup to meet
your local network configuration.
Enter the second menu page to configure the
Modbus parameters.
Содержание Rosemount X-Stream Series
Страница 370: ...Emerson Process Management GmbH Co OHG 7 82 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 ...
Страница 414: ...Emerson Process Management GmbH Co OHG 8 44 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 ...
Страница 486: ...Emerson Process Management GmbH Co OHG A 4 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 A 1 Modbus Specification ...
Страница 488: ...Emerson Process Management GmbH Co OHG A 6 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 A 1 Modbus Specification ...
Страница 490: ...Emerson Process Management GmbH Co OHG A 8 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 A 1 Modbus Specification ...
Страница 526: ...Emerson Process Management GmbH Co OHG A 44 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 ...
Страница 535: ......