Section 2:
Installation
April 2017
Instruction Manual
IM-106-880C, OI
26
COe 4-20 mA
Signal
2.4.5
COe 4-20 mA Signal
Another 4-20 mA signal at the AOUT 2 terminals represents the COe value.
2.4.6
Foundation Fieldbus Signal
The Foundation Fieldbus signal provides all output information and is accessible through a
Model 375 Handheld communicator.
2.4.7
Alarm Output Relay
Connect any customer-supplied relay input to the alarm output relay terminal. Use shielded wire
and terminate the shield at the electronics housing. The alarm output relay terminal is a set of
dry, no. 2, form C, contacts with 30 mA, 30 VDC capacity.
2.4.8
Remote Electronics Connections to Sensor Housing
Make the following connections between the remote electronics and sensor housings with the
electronics cable ordered with the package (
). Braided cable is available in lengths up
to 150 ft. (46 m).
NOTE
Interconnect wiring shown is for Rosemount supplied cables. For customer furnished
interconnect wiring or cables, refer to
2.4.9
Signal Connections
Connect the electronics housing terminals to the corresponding terminals in the sensor
housing. The twisted wire pairs are numbered on the inner plastic wrapper. Keep twisted pairs
together and match the numbers and wire colors shown in
2.4.10
Heater Power Connections
Use the blue, white, orange black, red, and yellow stranded wires in the heater power cable to
connect power to the three heaters in the sensor housing. Match the wire colors to the
corresponding heater power terminal blocks in the sensor and electronics housings as shown in
Содержание Rosemount OCX 8800
Страница 2: ......
Страница 41: ...Instruction Manual IM 106 880C OI Section 2 Installation April 2017 Section contents 17 ...
Страница 192: ...Section 7 Foundation Fieldbus April 2017 Instruction Manual IM 106 880C OI 16 6 About AMS and DeltaV Software ...
Страница 205: ...Alarm Relay Events April 2017 Instruction Manual IM 106 880C OI 17 8 Alarm Relay Events ...
Страница 251: ...Replace Tube Fittings April 2017 Instruction Manual IM 106 880C OI 22 4 Install Tube Fittings ...
Страница 259: ...Section 10 Replacement Parts April 2017 Instruction Manual IM 106 880C OI 23 2 O2 Cell and Heater Strut Assembly ...
Страница 261: ...Instruction Manual IM 106 880C OI Safety Data April 2017 Appendix contents 233 ...
Страница 263: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 235 ...
Страница 267: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 239 ...
Страница 271: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 243 ...
Страница 273: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 245 ...
Страница 275: ...Instruction Manual Safety Data IM 106 880C OI April 2017 IMPORTANT Safety Instructions 247 ...
Страница 277: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 249 ...
Страница 279: ...Instruction Manual Safety Data IM 106 880C OI April 2017 Safety Instructions 251 ...
Страница 298: ...SPA with HART Alarm April 2017 Instruction Manual IM 106 880C OI 27 2 Configuration Calibratio n ...
Страница 300: ...Instruction Manual IM 106 880C OI Index April 2017 Manual index 27 4 ...
Страница 304: ...Index April 2017 Instruction Manual IM 106 880C OI 27 8 Manual index ...
Страница 305: ......