6
Technical specifications
6.1
Detection ranges per detector/flame simulator
Table 6-1: Detection ranges per detector/flame simulator
Model
Detector types
Detector sensitivity
settings
Testing distance
Rosemount FS-HR-975
975HR (Legacy)
50 ft (15 m)
6.6 ft (2 m)
100 ft (30 m)
19.6 ft (6 m)
150 ft (45 m)
29.5 ft (9 m)
215 ft (65.5 m)
39.3 ft (12 m)
975HR
10 ft (3 m)
3 ft (1 m)
50 ft (15 m)
6.6 ft (2 m)
100 ft (30 m)
19.6 ft (6 m)
150 ft (45 m)
29.5 ft (9 m)
215 ft (65.5 m)
39.3 ft (12 m)
Note
•
The minimum distance from the detector is 30 in (75 cm).
•
At extreme temperatures, there is a 15 percent reduction in the testing range.
WARNING
Keep the device in a safe place when not in use.
6.2
General specifications
Temperature range: -4 °F (-20 °C) to 122 °F (50 °C)
Vibration protection: 1 g (10 - 50 Hz)
6.3
Electrical specifications
•
Rechargeable four cell lithium-ion battery:
—
Power: 14.8 V (4 x 3.7 V), maximum current: 0.2 A
—
Charging: 16.8 V (4 x 4.2 V), maximum current: 4 A
•
Battery capacity: 2.6 Ah
•
Charging time: Two hours at 2 A
Reference Manual
Technical specifications
00809-0900-4975
May 2022
Rosemount FS-HR-975
21
Содержание Rosemount FS-HR-975
Страница 1: ...Reference Manual 00809 0900 4975 Rev DD May 2022 Rosemount FS HR 975 Flame Simulator ...
Страница 4: ...4 ...
Страница 6: ...Contents Reference Manual May 2022 00809 0900 4975 6 Emerson com Rosemount ...
Страница 14: ...Operation Reference Manual May 2022 00809 0900 4975 14 Emerson com Rosemount ...
Страница 18: ...Maintenance Reference Manual May 2022 00809 0900 4975 18 Emerson com Rosemount ...
Страница 20: ...Ordering information Reference Manual May 2022 00809 0900 4975 20 Emerson com Rosemount ...
Страница 26: ...Product certifications Reference Manual May 2022 00809 0900 4975 26 Emerson com Rosemount ...