Installing the detector
This chapter provides basic guidelines for installing the detector. It does not attempt to
cover all of the standard practices and codes of installation. Rather, it emphasizes specific
points of consideration and provides some general rules for qualified personnel. Wherever
applicable, special safety precautions are stressed.
2.1
General guidelines
To ensure optimal performance and an efficient installation, consider the following
guidelines:
•
Sensitivity: To determine the level of sensitivity, consider the following:
—
Size of fire at the required distance to be detected
—
Type of flammable materials
•
Wiring:
—
The wire gauge must be designed according to the distance from the detector to
the controller and the number of detectors on the same power line. See
.
—
To fully comply with EMC directive and protect against interference caused by RFI
and EMI, the cable to the detector must be shielded, and the detector must be
grounded. Ground the shield at the detector end.
•
Spacing and location: The number of detectors and their locations in the protected
area are determined by:
—
Size of the protected area
—
Sensitivity of the detectors
—
Obstructed lines of sight
—
Cone of view of the detectors
•
Environment:
—
Dust, snow, or rain can reduce the detector's sensitivity and require more
maintenance activities.
—
The presence of high intensity flickering IR sources may affect sensitivity.
•
Aiming the detector:
—
Aim the detector toward the center of the detection zone and make sure the view
of the protected area is completely unobstructed.
—
Whenever possible, tilt the detector face down at a 45-degree angle to maximize
coverage and prevent accumulation of dust and dirt.
—
Take into account all conceivable considerations regarding detection location
before starting an installation.
Installations must comply with NFPA 72E or any other local and international regulations
and standards, as applicable to flame detectors and installation of Ex approved products.
Reference Manual
Installing the detector
00809-0100-4975
August 2019
Rosemount 975MR
25
Содержание Rosemount 975MR
Страница 38: ...Installing the detector Reference Manual August 2019 00809 0100 4975 38 Emerson com Rosemount ...
Страница 46: ...Maintenance and troubleshooting Reference Manual August 2019 00809 0100 4975 46 Emerson com Rosemount ...
Страница 52: ...Specifications and reference data Reference Manual August 2019 00809 0100 4975 52 Emerson com Rosemount ...
Страница 60: ...RS 485 communication network Reference Manual August 2019 00809 0100 4975 60 Emerson com Rosemount ...
Страница 67: ...Figure D 4 Duct Mount Reference Manual Accessories 00809 0100 4975 August 2019 Rosemount 975MR 67 ...
Страница 70: ...Accessories Reference Manual August 2019 00809 0100 4975 70 Emerson com Rosemount ...