![Emerson Rosemount 975HR Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/emerson/rosemount-975hr/rosemount-975hr_reference-manual_104225023.webp)
•
Relays (alarm, fault, auxiliary)
•
RS-485 Modbus
®
Table 1-6: Available Output Types
Output type
Version
Detector status
Alarm relay
975HR- output configurations
1AXXXXX, 1RXXXXX, and
2RXXXXX
The relay is N.O.
975HR - output configurations
2AXXXXX and 3AXXXXX
The relay is N.O. and N.C.
Auxiliary relay
975HR - output configurations
1AXXXXX, 2AXXXXX, and
1RXXXXX
The relay is N.O.
Fault relay
975HR - output configurations
1AXXXXX, 2AXXXXX, and
1RXXXXX
The relay is N.C. energized.
975HR - output configurations
3AXXXXX and 2RXXXXX
The relay is N.O. energized.
0-20 mA current output
975HR - output configuration
1AXXXXX
Sink with the HART protocol
(can be changed to Source - see
,
, and
).
975H - output configurations
2AXXXXX and 3AXXXXXR
Source with the HART protocol
RS-485
All versions
Modbus protocol
1.5.6
Detector status
The possible detector function statuses are listed in the table below. Use HART
®
or
Modbus
®
to see a more detailed fault analysis.
Table 1-7: Detector Statuses
Status
Description
Normal
Normal operation.
BIT
Built-in test being performed.
Warning
Fire detected - changed to
Warning
(pre-alarm state).
Alarm
Fire detected - changed to
Fire Alarm
state.
Latched alarm (optional)
The alarm outputs remain latched on following detection of a fire
that has already been extinguished.
BIT fault
A fault is detected during built-in test sequence or other electric
failure. The detector will continue to detect for fire.
Fault
A fault is detected when the power supply is too low or due to a
software fault or electrical failure. The detector will
not
detect fire
in this condition.
Reference Manual
Introduction
00809-0100-4976
June 2021
Rosemount 975HR
23
Legacy
Содержание Rosemount 975HR
Страница 28: ...Introduction Reference Manual June 2021 00809 0100 4976 28 Emerson com Rosemount L e g a c y ...
Страница 42: ...Installing the detector Reference Manual June 2021 00809 0100 4976 42 Emerson com Rosemount L e g a c y ...
Страница 66: ...RS 485 communication network Reference Manual June 2021 00809 0100 4976 66 Emerson com Rosemount L e g a c y ...