If this occurs, it is due to blockage, very low signal, partial obscuration, or full beam
block. In this situation, detection is no longer possible. The detector's proper operation
can be restored (auto reset) during operation if the condition causing the problem is
removed or resolved. This mode occurs after a delay of 60 seconds from the moment
of the fault. This delay is important to eliminate momentary obscuration due to
passing through the beam.
•
Fault 2 (1 mA output) - critical
In this case, the detector is disabled due to electrical/software operational failure,
central device (memory or processor) fault, or low voltage. This fault causes the
detector to cease operation.
If there is a fault in the 0-20 mA loop, the output is 0 mA.
3.1.4
Zero calibration mode (1 mA output)
This mode zeroes the base level from which the detector reads gas.
Only do this when:
•
No gases are present.
•
There is a clear path between the source and the detector.
•
Weather conditions are clear.
Use a field communicator or host software on your personal computer (PC) to zero
calibrate after installation, re-alignment, and window cleaning. While the device is
connected to the field communicator, you can also use the magnetic mode selector for
zero calibration.
Related information
3.2
Visual indicators
One three color LED indicator is located in the back side of the detector/source and can be
seen through the back cover window.
The detector statuses are listed in
Table 3-1: Detector LED indications
Detector status
LED color
LED mode
Fault
Yellow
4 Hz - flashing
Alignment / Standby
Yellow
1 Hz - flashing
Zero calibration
Yellow
Constant
Normal
Green
1 Hz - flashing
Warning
Red
2 Hz - flashing
Alarm
Red
Constant
Operating modes
Reference Manual
May 2022
00809-0100-4035
18
Emerson.com/Rosemount
Содержание Rosemount 935
Страница 1: ...Reference Manual 00809 0100 4035 Rev AH May 2022 Rosemount 935 Open Path Combustible Gas Detector ...
Страница 8: ...Product overview Reference Manual May 2022 00809 0100 4035 8 Emerson com Rosemount ...
Страница 16: ...Technical description Reference Manual May 2022 00809 0100 4035 16 Emerson com Rosemount ...
Страница 22: ...Operating modes Reference Manual May 2022 00809 0100 4035 22 Emerson com Rosemount ...
Страница 46: ...Operation Reference Manual May 2022 00809 0100 4035 46 Emerson com Rosemount ...
Страница 48: ...10 Do a functional check Maintenance Reference Manual May 2022 00809 0100 4035 48 Emerson com Rosemount ...
Страница 52: ...Troubleshooting Reference Manual May 2022 00809 0100 4035 52 Emerson com Rosemount ...
Страница 56: ...Ordering information Reference Manual May 2022 00809 0100 4035 56 Emerson com Rosemount ...
Страница 62: ...Specifications Reference Manual May 2022 00809 0100 4035 62 Emerson com Rosemount ...
Страница 70: ...Wiring configurations Reference Manual May 2022 00809 0100 4035 70 Emerson com Rosemount ...
Страница 74: ...Support Reference Manual May 2022 00809 0100 4035 74 Emerson com Rosemount ...