2
Configure the transducer block
The LCD display transducer block can be configured to sequence eight
different process variables. If a function block is scheduled in the Rosemount
752 that links a process variable from another device on the segment, that
process variable can be displayed on the LCD display.
To configure the Rosemount 752 Fieldbus Indicator use any F
OUNDATION
Fieldbus configuration tool to modify the configuration parameters for each
value that is to be displayed.
2.1 Configuration parameters
Note
Some host systems may ask for the device's capability level during
commissioning. If prompted, the correct value to enter for the Rosemount
752 is 1.
DISPLAY_PARAM_SEL
The DISPLAY_PARAM_SEL parameter specifies how many process variables
willbe displayed. Select up to eight display parameters.
BLK_TAG_#
Enter the Block Tag of the function block that contains the parameter to be
displayed. The default function block tags from the factory are:
•
PID_1200_XXXX
•
ISEL_1300_XXXX
•
CHAR_1400_XXXX
•
ARITH_1500_XXXX
•
INTEG_1600_XXXX
Note
XXXX represents the last four digits of the device ID.
BLK_TYPE_#
Enter the Block Type of the function block that contains the parameter to be
displayed. (e.g. ISEL PID, etc.)
PARAM_INDEX_#
Choose the parameter to be displayed.
February 2019
Quick Start Guide
Quick Start Guide
7